CITY OF FORT ST. JOHN
Fire Prevention Bylaw No. 2106, 2012
A BYLAW TO REGULATE FIRE PROTECTION AND LIFE SAFETY
AND PROVIDE EMERGENCY SERVICES
WHEREAS the Council of the City of Fort St. John may, by bylaw pursuant to Sections 8(3)(g),
63 and 66 of the Community Charter, S.B.C. 2003, c. 26, ("Community Charter") prohibit,
impose requirements and establish regulations for the protection of persons and property and
authorize the Fire Chief and members of the Fire Rescue Department to exercise certain
powers;
AND WHEREAS the Council of the City of Fort St. John may, by bylaw, impose fees pursuant to
Sections 194 and 196 of the Community Charter;
AND WHEREAS the Council of the City of Fort St. John may by bylaw, pursuant to Section 154
of the Community Charter delegate its powers, duties and functions to an officer or employee of
the City;
AND WHEREAS the Council of the City of Fort St. John may, by bylaw regulate, prohibit and
impose requirements in relation to burning pursuant to Sections 8(3)(i) and (h), 15 and 64(a)
and (c) of the Community Charter and in relation to municipal services pursuant to section
8(3)(a) of the Community Charter;
THEREFORE BE IT RESOLVED that the Council of the City of Fort St. John, in open meeting
assembled, ENACTS AS FOLLOWS:
Table of Contents
SECTION - TOPIC
1.
Title
2.
Definitions
PART 1 - ADMINISTRATION
3.
Provincial Fire Code Adopted
4.
Confirmation of Fire Rescue Department
5.
Confirmation and Appointment of Fire Chief
6.
Responsibilities and Duties of Fire Chief
7.
Appointment and Accountability of Officers and Members
8.
Rank Structure of Fire Rescue Department
9.
Jurisdiction of Fire Rescue Department
10.
Fees
PART 2 - FIRE INCIDENT RESPONSES AND OPERATIONS
11.
Control, Direction and Management
12.
Authorization to Enter Property
13.
Regulations at Incident
-
Fire Hose
-
Assistance in the Fighting of Fires
-
Evacuation of Buildings and Hazard Areas
-
Demolition of Adjacent Buildings or Structures
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 2
Table of Contents
PART 2 - FIRE INCIDENT RESPONSES AND OPERATIONS (continued)
13.
Regulations at Incident (continued)
-
Securing Vacant Buildings and Structures Where Fire Has Occurred
-
Commandeering of Privately Owned Equipment
-
Compliance with Direction
PART 3 - FIRE PREVENTION
14.
Prevention of Fire Hazards
- Fire Hazards
- Remediation of Fire Hazards
- Securing of Vacant Buildings, Structures and Properties where Fire
Hazard
PART 4 - INSPECTIONS UNDER FIRE SERVICES ACT
15.
Frequency of Inspections Delegated
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
16.
Fire Drills
17.
Fire Safety Plans
18.
Pre-Incident Plan
19.
Smoke and Fire Alarms and Sprinklers
20.
Containers for Collection of Combustible Refuse
21.
Storage of Flammable or Combustible Materials
22.
Fuel Tanks for Flammable or Combustible Liquids
23.
Exit and Fire Doors
24.
Exit and Access Requirements
25.
Fire and Life Safety Equipment Orders
26.
Evacuation or No Occupancy Order
27.
Fire Protection Technician's Obligations
28.
Fire Alarm Systems
- Contact Persons for Fire Alarm Systems
PART 6 - BURNING REQUIREMENTS & FIREWORK PERMITS
29.
Open Burning
30.
Burning Permits
31.
Fireworks
PART 7 - FIRE HYDRANTS AND FIRE CONNECTIONS
32.
General Requirements
33.
Maintenance & Inspections
34.
Service After Each Use
35.
Semi-Annually Inspection
36.
Annually Servicing
37.
Three Year Servicing
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 3
Table of Contents
PART 8 - STREET ADDRESSES
38.
Civic Street Numbers
PART 9 - INTERPRETATION AND PENALTIES
39.
Schedules
40.
Severability
41.
Penalties and Enforcement
42.
Repeal
SCHEDULES
SCHEDULE A
Fees
SCHEDULE B
Emergency Contact Person Form
SCHEDULE C
Fort St. John Fire Rescue Department Order
SCHEDULE D
Evacuation Order
SCHEDULE E
Burning Permit
SCHEDULE F
Private Fire Hydrant Service Report
SCHEDULE G
Application to Remove, Install, Repair or Upgrade a Fuel Storage Tank and
Piping (Commercial Property)
SCHEDULE H
Municipal Ticket Information Offences
SCHEDULE I
Declaration of On Site Chemicals and Hazardous Materials
1.
Title
This Bylaw may be known and cited as "FIRE PROTECTION AND LIFE SAFETY
REGULATION BYLAW NO. 2106, 2012".
2.
Definition
Unless otherwise defined as follows, or the context otherwise requires, all words and
phrases in this Bylaw shall be construed in accordance with the meaning assigned to
them in the Building Code, Fire Services Act and Fire Code.
"APPARATUS"
means any vehicle provided with machinery, devices,
equipment or materials for firefighting as well as vehicles
used to transport fire fighters or supplies.
"BUILDING CODE"
means the British Columbia Building Code as amended from
time to time.
"BUILDING"
means a structure that is used or intended to be used for the
support enclosure and/ or the shelter of persons, animals or
property, except those prescribed by regulation as exempted
from the Building Code.
"CITY PARK"
means any community park operated and maintained by the
City.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 4
2.
Definition (continued)
"CITY"
means the City of Fort St. John.
"COMBUSTIBLE
LIQUID"
means any liquid having a flash point at or above 37.8
degrees Celsius and below 93.3 degrees Celsius.
"COMBUSTIBLE
REFUSE"
means any combustible materials that are to be landfilled or
recycled.
"CONSTRUCTION
MATERIAL"
means any waste or refuse created by the clearing of land, or
the construction, repair or demolition of a Building or
Structure, including without limitation, trees, branches,
stumps and roots.
"CONTACT PERSON"
means a person designated by the occupier or owner of a
Building or Structure at which a Fire Alarm System is installed
who is able to attend at the Building or Structure when the
Fire Alarm System has been activated.
"COUNCIL"
means the Municipal Council of the City of Fort St. John.
"EQUIPMENT"
means any tools, contrivances, devices or materials used by
the Fire Rescue Department at any Incident or other
emergency.
"FALSE ALARM"
means the activation of a fire alarm system resulting in the
direct or indirect notification of the Fire Rescue Department to
attend the address of the Fire Alarm System, where there is
in fact no Incident at that address.
"FIRE ALARM
SYSTEM"
means all equipment, including without limitation, batteries,
alarm gongs, horns, buzzers, switches, wiring, relay
equipment, sensors, and other accessories designed to issue
a warning of a fire by activating an audible alarm signal or
alerting a monitoring service but does not include a fire alarm
or smoke detector that is intended to alert only the occupants
of a single dwelling unit.
"FIRE AND LIFE
SAFETY EQUIPMENT"
includes but is not limited to: Fire Alarm Systems, automatic
Sprinkler Systems, special extinguishing systems, portable
extinguishers, emergency lighting, water supply systems for
fire protection, standpipe and hose systems, smoke control
measures,
emergency
power
installations,
voice
communication systems and fire fighter elevators.
FIRE CHIEF"
means a person appointed by resolution of Council to be in
charge of the Fire Rescue Department, and includes the
Deputy Fire Chief and any other person authorized to act on
behalf of the Fire Chief.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 5
2.
Definition (continued)
"FIRE CODE"
means the British Columbia Fire Code as amended from time
to time.
"FIRE PREVENTION
OFFICER"
means a member the Fire Rescue Department authorized in
writing by the Fire Chief to be a Fire Prevention Officer and a
Local Assistant Fire Commissioner.
"FIRE PROTECTION
TECHNICIAN"
means a person who has provided the Fire Rescue
Department
with
acceptable
documentation
from
a
manufacturer of Fire and Life Safety Equipment certifying that
he or she has been trained to install and service their
equipment or from the agency known as the Applied Science
Technologist and Technicians of British Columbia certifying
that he or she is able to perform inspections and testing on
fire extinguishers, Fire Alarm Systems, Sprinkler systems,
and other Fire and Life Safety Equipment or a person
approved by the Fire Chief.
"FIRE RESCUE
DEPARTMENT"
means the City of Fort St. John Fire Rescue Department.
"FIRE SAFETY PLAN"
is a set of emergency procedures and guidelines to be
followed by the occupants of a Building in the event of a fire
or an emergency in a Building or Structure; and may include
the locations of utilities and emergency shutoffs for gas and
water, and operational information of Fire and Life Safety
Equipment.
"FIRE SERVICES ACT"
means the Fire Services Act, R.S.B.C. 1996, c.144.
"FIREFIGHTER"
means every Member of the Fire Rescue Department other
than an Officer, whose duties include fire prevention, fire
suppression, or emergency response.
"INCIDENT"
means a fire or any other class of circumstance that may
cause harm to persons or property and includes rescue,
medical aid, hazardous material incidents or other similar
situations that are a threat to life.
"MEMBER"
means any person that is duly appointed by the Fire Chief as
a member of the Fire Rescue Department and is an
employee of the City.
"OCCUPANCY"
means the use or intended use of a Building or part thereof
for the shelter or support of persons, animals or property.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 6
2.
Definition (continued)
"OFFICER"
means any member of the Fire Rescue Department holding
the rank of:
(a)
Fire Chief
(b)
Deputy Fire Chief
(c)
Captain
(d)
Lieutenant
(e)
Fire Prevention Officer
"OFFICER IN
COMMAND"
means the highest-ranking Officer in attendance at an
Incident. In the event that an Officer is not in attendance at an
Incident, the most senior Member in attendance at that
Incident will assume command in accordance with Section
11(1).
"OPEN BURNING"
means a fire in the open air but does not include a Cooking
Fire or a fire where the products of combustion from the fire
are conveyed to and disposed of by means of a chimney in a
Building or Structure constructed and maintained in
accordance with the Building Code.
"PEACE OFFICER"
means any RCMP member or a Bylaw Enforcement Officer.
"PREMISES"
means a Building or Structure together with its grounds and
appurtenances or a vacant lot.
"PRE-INCIDENT PLAN"
means a series of documents containing plans, drawings and
written descriptions identifying the type and location of
Buildings,
firefighting
hazards,
Fire
and
Life
Safety
Equipment and utilities".
"PRIVATE HYDRANT"
means a fire hydrant on private property or common property
within a strata property.
"SINGLE DWELLING
UNIT"
is a suite operated as a housekeeping unit under a single
tenancy.
"SMOKE ALARM"
means a combined smoke detector and audible alarm device
designed to sound an alarm within the room in which it is
located upon the detection of smoke within the room.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 7
PART 1 - ADMINISTRATION
3.
Provincial Fire Code Adopted
Pursuant to Section 15 of the Community Charter, the Council adopts and establishes
for the City the Fire Code. The provisions of the Fire Code adopted and established are
made part of this Bylaw and shall be considered as provisions of this Bylaw.
4.
Confirmation of Fire Rescue Department
The Fire Rescue Department as established is hereby confirmed.
5.
Confirmation and Appointment of Fire Chief
(1)
The position of Fire Chief as established is hereby confirmed.
(2)
The Fire Chief shall be appointed by a resolution of Council.
6.
Responsibilities and Duties of Fire Chief
(1)
The Fire Chief is the Director of the Fire Rescue Department and is responsible
for the efficient management of all Members, Apparatus, Equipment, responses
to Incidents and the provision of fire prevention and protection services to the
City. The Fire Chief shall ensure that the Fire Rescue Department is staffed with
Members in accordance with Council policy and direction.
(2)
The Fire Chief shall establish rules, regulations and policies necessary for the
proper organization, administration and operation of the Fire Rescue Department
including but not limited to:
2.
Definition (continued)
"SPRINKLER SYSTEM"
includes all equipment forming part of or used in connection
with a fire sprinkler system, including without limitation, all
heads, valves, piping, switches, sensors, relay equipment
and other accessories.
"STRUCTURE"
means any construction, or any production or piece of work
artificially built up or composed of parts joined together in
some definite matter; that which is built or constructed, an
edifice or building of any kind whether fixed to, supported by
or sunk into land or water including combinations of materials
to form a construction for Occupancy, use or ornamentation
whether installed on, above, or below the surface of a parcel
of land but specifically excludes landscaping, fences, paving
and retaining structures less than 1.5 meters in height.
"VEHICLE"
means a device in, upon, or by which a person or thing is or
may be transported or drawn upon a highway, except a
device designed to be moved by human power or used
exclusively upon stationary rails or tracks.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 8
PART 1 - ADMINISTRATION
6.
Responsibilities and Duties of Fire Chief (continued)
(a)
the use, care and protection of Fire Rescue Department property;
(b)
the conduct and discipline of Members of the Fire Rescue Department;
(c)
the safe and efficient operation of the Fire Rescue Department; and
(d)
the duties and responsibilities of Members.
(3)
The Fire Chief shall take responsibility for all fire protection matters and other
Incidents including the enforcement of applicable sections of the Fire Services
Act and its regulations, and the Fire Code and shall assume the responsibilities
of a local assistant to the Fire Commissioner.
(4)
The Fire Chief may appoint or designate other Officers of the Fire Rescue
Department to act as Fire Chief on his behalf and may, in writing, authorize
Officers to exercise the powers of a local assistant to the Fire Commissioner.
(5)
Council authorizes the Fire Chief to exercise all the powers of the Fire
Commissioner under section 25 of the Fire Services Act and for these purposes
that section applies.
7.
Appointment and Accountability of Officers and Members
(1)
All Members of the Fire Rescue Department shall be appointed by the Fire Chief.
(2)
Officers shall be appointed by the Fire Chief, as vacancies occur or as needs
dictate, from firefighters meeting the qualifying standards.
(3)
Members are accountable to the Fire Chief for the actions and affairs of the
members under their command.
(4)
All Officers are responsible for ensuring that Members adhere to any and all
applicable City and Fire Rescue Department policies, procedures, rules and
regulations.
8.
Rank Structure of Fire Rescue Department
The rank structure of the Fire Rescue Department, in descending order shall be as
follows:
(a)
Fire Chief;
(b)
Deputy Fire Chief;
(c)
Captain;
(d)
Lieutenant;
(e)
Fire Prevention Officer;
(f)
Firefighter;
(g)
On Call Firefighter.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 9
PART 1 - ADMINISTRATION
9.
Jurisdiction of Fire Rescue Department
The limits of the jurisdiction of the Fire Rescue Department will extend to the area and
boundaries of the City of Fort St. John, and neither the Fire Chief or Members shall
supply firefighting services or respond to an Incident nor shall any part of the fire
Apparatus or Equipment be used outside the boundaries of the City without:
-
prior approval of City Council as well as written consent from the other local
government and includes confirmation of cost reimbursement, or
-
expressed authority of a written agreement between the City and the other local
government providing for the supply of firefighting services, or other Incident
response outside the City boundaries.
10.
Fees and Municipal Ticket Offences
A person must pay a fee as prescribed in Schedule "A" or a fine as prescribed in
Schedule "H" attached to and forming part of this Bylaw:
(a)
a search of City files for any Fire Code violations, inspection infractions or
information about environmental contamination existing on the Premises;
(b)
a Fire Rescue Department inspection of a Building, Premises or property that is
not a regularly scheduled inspection, and the fee is payable by the person who
requested the inspection;
(c)
Fire Extinguisher Training Course, however, the fee may be discounted one
hundred (100) percent if the Fire Extinguishing Training course is given to a
non-profit Society;
(d)
a re-inspection of a Building, Premises or property where the Fire Prevention
Officer finds that an owner or occupier has not complied with a Fire Rescue
Department Order;
(e)
a third inspection of a Building, Premises or property by a Fire Prevention Officer
that is required because the owner or occupier has failed to comply with the
requirements in an inspection report;
(f)
the Fire Rescue Department response to a False Alarm where it is the second or
greater number of False Alarms originating from one Fire Alarm system in
accordance with the City's False Alarm Bylaw No. 1615, 2003 as amended from
time to time;
(g)
a Burning Permit; and
(h)
a Fuel Tank Permit.
PART 2 - FIRE INCIDENT RESPONSES AND OPERATIONS
11.
Control, Direction and Management
The Fire Chief or Officer In Command at an Incident shall have control, direction and
management of all Fire Rescue Department Apparatus, Equipment, and Members
assigned to an Incident and, where an Officer In Command is in charge, he shall
continue to act in that capacity until relieved by a more senior Officer.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 10
PART 2 - FIRE INCIDENT RESPONSES AND OPERATIONS
12.
Authorization to Enter Property
(1)
The Fire Chief and Members are authorized to enter onto property and inspect
Premises, with or without Apparatus and Equipment, for conditions that may
cause a fire, increase the danger of a fire or increase the danger to persons or
property from a fire.
(2)
The Fire Chief and Members are authorized to enter onto property and into
Buildings or Structures to inspect and determine whether all regulations,
prohibitions and requirements are being met in relation to any matter contained in
this Bylaw, the Fire Services Act and its regulations and the Fire Code.
(3)
The Fire Chief and Members are authorized to enter onto property and into
Buildings or Structures, including those adjacent to an Incident, with or without
Apparatus and Equipment, to take measures to prevent and suppress fires or
deal with another form of Incident.
13.
Regulations at Incident
Fire Hose
(1)
No person shall drive over, or be within nine (9) meters of a Fire Rescue
Department hose that is in use or filled with water, without the permission of the
Officer in Command at an Incident.
Assistance in the Fighting of Fires
(2)
The Officer in Command is authorized to require a person to assist in the fighting
of any fire or in the preserving of any property threatened by fire, or to assist in
the salvaging and safeguarding of property threatened by fire.
Evacuation of Buildings and Hazard Areas
(3)
The Fire Chief is authorized to order the evacuation of any Building or area
where there is an emergency arising from a fire hazard, risk of explosion. In such
a case no person, other than the Fire Chief, the Officer In Command, a Member
of the Fire Rescue Department, or other person authorized by the Fire Chief or
Officer In Command shall remain in or shall enter those Buildings or areas.
Demolition of Adjacent Buildings or Structures
(4)
The Fire Chief or Officer In Command at any Incident is authorized to prevent
and suppress a fire by pulling down or demolishing a Building or Structure when
he considers it necessary to prevent or suppress any fire.
Securing Vacant Buildings and Structures Where Fire Has Occurred
(5)
If requested by an Officer, a property owner or occupier shall secure a Premises
that has been damaged by fire, in a manner approved by the Officer which will
include but not be limited to one or more of the following:
(a)
boarding up the Building or Structure;
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 11
PART 2 - FIRE INCIDENT RESPONSES AND OPERATIONS
13.
Regulations at Incident (continued)
Securing Vacant Buildings and Structures Where Fire Has Occurred (continued)
(b)
fencing; and/or
(c)
supply twenty-four (24) hour security services by a licensed security
company.
(6)
If the property owner or occupier cannot be located or fails to undertake the
securing of any Premises damaged by fire, the City will carry out the work of
securing the Premises and the costs will be billed to the property owner and, if
unpaid by December 31st in the year that the property owner or occupier failed to
take the required action, will be added to and form part of the property taxes in
relation to the Premises.
Commandeering of Privately Owned Equipment
(7)
The Fire Chief or Officer In Command at any Incident is hereby empowered to
commandeer privately owned equipment which he considers necessary to deal
with such Incident.
Compliance with Direction
(8)
No person shall fail to comply with a direction of the Officer In Command, or any
Member of the Fire Rescue Department made in accordance with this Bylaw at
an Incident.
(9)
No person shall interfere with or impede the use of Equipment by the Fire Chief
or a Member at an Incident.
PART 3 - FIRE PREVENTION
14.
Prevention of Fire Hazards
Fire Hazards
(1)
No person, being an owner or occupier of any Premises shall:
(a)
maintain the Premises in such a state of disrepair that a fire starting in
them might spread rapidly to endanger life or other property;
(b)
use or occupy the Premises in such a manner that fire would endanger
life or property or increase the danger of fire;
(c)
keep combustible or explosive material on the Premises, except as
permitted by this Bylaw or other enactment, or allow other flammable
conditions to exist in the Premises so as to endanger life or property;
(d)
allow a fire hazard to exist on the Premises.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 12
PART 3 - FIRE PREVENTION
14.
Prevention of Fire Hazards (continued)
Remediation of Fire Hazards
(2)
Where an Officer determines that one or more conditions as indicated in Section
14(1)(a), (b), (c), or (d) exists, the Officer may issue to an owner or occupier of a
Premises a Fire Rescue Department Order which is attached to and forms part of
this Bylaw as Schedule "C", requiring the owner or occupier of the Premises to
do one or more of the following:
a)
Repair the Building or Structure on the Premises;
b)
Remove or destroy the Building or Structure on the Premises;
c)
Alter the use or Occupancy of the Premises;
d)
Remove combustible or explosive material from the Premises or remedy
a flammable condition at the Premises;
e)
Remove or take any precautions required against the fire hazard present
at the Premises.
(3)
An Officer may specify a date by which the owner or occupier of the Premises
must comply with the Fire Rescue Department Order.
(4)
Should the owner or occupier of the Premises having received a Fire Rescue
Department order in accordance with section 14(2) fail to comply with the terms
of the Order, the City may carry out the work associated with the terms of the
Order and the costs of doing so will be billed to the owner or occupier of the
Premises. If unpaid by December 31 in the year in which the owner or occupier
failed to take the required action under the Order, will be added to and form part
of the property taxes on the property owner's Premises.
(5)
If a Fire Rescue Department Order is issued under section 14(2), the owner or
occupier of a Premises may appeal to the Fire Chief in writing within seven (7)
days after receipt of the Order and the Fire Chief will promptly investigate the
appeal and, in writing, either affirm, modify or revoke the Fire Rescue
Department Order issued under section 14(2).
Securing of Vacant Buildings, Structures and Properties where Fire Hazard
(6)
If directed by the Fire Chief or Officer, a property owner shall secure a vacant
Building, Structure or property which contains a fire hazard or has been used or
occupied so as to create a fire hazard, in a manner approved by the Fire Chief or
Officer, which shall include, but not be limited to one or more of the following:
(a)
boarding up the Building or Structure;
(b)
fencing; and/or
(c)
supplying twenty-four (24) hour security services by a licensed security
company.
(7)
Should the property owner fail to undertake the securing of any Building,
Structure or property as required in accordance with section 14(4), the City will
carry out the work and the costs of doing so will be billed to the property owner.
If unpaid by December 31st in the year in which the property owner failed to take
the required action, will be added to and form part of the property taxes on the
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 13
PART 3 - FIRE PREVENTION
14.
Prevention of Fire Hazards (continued)
Securing of Vacant Buildings, Structures and Properties where Fire Hazard (continued)
property owner's property.
PART 4 - INSPECTIONS UNDER FIRE SERVICES ACT
15.
Frequency of Inspections Delegated
(1)
The authority and duty of the Council under the Fire Services Act to establish,
revise and implement a regular system of inspections of hotels, public buildings,
churches, theatres, halls, or other Buildings used as a place of public resort in
the City is delegated to the Fire Chief in accordance with Fire Inspection Council
Policy No. 29/12.
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
16.
Fire Drills
(1)
The owner or occupier of a hotel, hospital, community care facility or other
Building with sleeping accommodation and used for the care of persons, must
adopt, and have employees in the Building practice a fire drill system in
accordance with the Fire Code.
(2)
The owner or occupier of a school, child care facility, children's home or other
institution for children's education or care, shall adopt and have all persons in
these Premises practice a fire drill system in accordance with the Fire Code.
17.
Fire Safety Plans
(1)
The owner or occupier of a Building or Structure that has a Fire Alarm System
shall submit a Fire Safety Plan annually in a form acceptable to the Fire Chief.
(2)
The owner or occupier of a Building or Structure who has submitted a Fire Safety
Plan to the Fire Chief shall each year, before the expiry of one (1) year from the
last approval of Fire Safety Plan, revise and resubmit it to the Fire Chief if any
changes are necessary as a consequence of changes to the Building, utilities or
Fire and Life Safety Equipment.
(3)
The owner or occupier of a Building or Structure who has submitted a Fire Safety
Plan to the Fire Chief must post a notice visible to all occupants of the Building or
Structure of the location where a copy of the current Fire Safety Plan may be
reviewed by the occupants.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 14
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
18.
Pre-Incident Plan
(1)
An owner of a Building without a Fire Alarm System, other than a Single Dwelling
Unit, duplex, triplex up to and including a four plex or where each suite has direct
access to an exterior exit facility leading to ground level shall submit a current
Pre-Incident Plan annually in a form acceptable to the Fire Chief.
(2)
The owner of a Building or Structure who has submitted a Pre-Incident Plan to
the Fire Chief shall each year, before the expiry of one (1) year from the last
approval of this Pre-Incident Plan, revise and resubmit it to the Fire Chief if any
changes are necessary as a consequence of changes to the Building, utilities or
Fire And Life Safety Equipment.
19.
Smoke and Fire Alarms and Sprinklers
(1)
Where required by the Building Code, an owner or occupier of a Building shall
install, or cause to be installed, Sprinkler Systems, fire alarms and Smoke Alarms
in accordance with the Building Code Standards.
20.
Containers for Collection of Combustible Refuse
(1)
All containers used for the collection of Combustible Refuse in quantities
exceeding five cubic feet shall be constructed of solid sheet non-combustible
material.
(2)
Each container referred to in section 20(1) shall have easy closing lids that must
be operational at all times. Lids may be constructed of heavy plastic.
(3)
Containers referred to in section 20(1) shall be located at least ten feet from any
Building or fuel supply tank unless otherwise approved by the Fire Chief.
(4)
Containers that are intended for temporary collection of combustible Construction
Material are exempt from section 20(2) and 20(3) of this Bylaw.
21.
Storage of Flammable or Combustible Materials
(1)
No person shall store clean up rags or shop towels for products subject to
spontaneous combustion except in a non-combustible container referred to in
section 20(1) with tight fitting self-closing metal lid.
(2)
No person shall allow lids to remain open on any container referred to in 20(1)
that contains clean-up rags or shop towels that are subject to spontaneous
combustion.
(3)
An owner or occupier of a premise shall store flammable or Combustible Liquids
or products in accordance with this Bylaw and the Fire Code.
(4)
Each owner or occupier of a building or structure that stores chemicals or
hazardous materials must fill out and submit a Declaration of on Site Chemicals
and Hazardous Materials Form to the Fire Rescue Department. This form is
attached to and forms part of this bylaw as Schedule "I".
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 15
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
22.
Fuel Tanks for Flammable or Combustible Liquids
An owner or occupier of the Premises may not undertake installation, removal, repair or
upgrade to an underground or aboveground fuel oil tank of any size over 2500 litres
(550 gal) or install, remove, replace or repair fuel distribution piping or dispensing
equipment unless the owner or occupier of the Premises first obtains a permit from the
Fire Rescue Department in the form attached to and forming part of this Bylaw as
Schedule "G".
23.
Exit and Fire Doors
(1)
The owner or occupier of a hotel, public Building, church or Building to which the
public is invited shall ensure that the smoke and fire doors are kept closed when
not in use for access unless they are automatically controlled to close by a
system approved by the Fire Chief.
(2)
No person shall alter or install exit doors in a church, hotel, public Building or
Building to which the public is invited unless they open freely outward and the
alterations or installations are approved by the Fire Chief.
(3)
No person shall install locking devices on any required exit doors in a hotel,
public Building, church or Building to which the public is invited unless the locking
devices are approved by the Fire Chief.
24.
Exit and Access Requirements
(1)
No person shall install a fire lane gate without review and approval by the Fire
Rescue Department prior to installation.
(2)
No owner or occupier of a premises shall block any primary or secondary
vehicular access with a gate without review and approval by the Fire Rescue
Department prior to installation.
(3)
The owner or occupier of a hotel or public Building shall install or cause to be
installed in all main halls and at the intersection of all cross halls of the hotel or
public Building conspicuous signs indicating the means of exit where required by
and in accordance with the Building Code.
(4)
The owner or occupier of a hotel or public Building shall post or cause to be
posted in each room a conspicuous notice describing the means of exit, with
instructions to be followed in the event of fire where required by and in
accordance with the Building Code.
(5)
An owner or occupier of a hotel or public Building shall ensure that the means of
exit are illuminated where required by and in accordance with the Building Code.
(6)
No person shall sit, stand, place, or leave any article, thing or matter in such a
manner as to interfere with the means of ingress and egress inside or outside
any Building.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 16
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
25.
Fire and Life Safety Equipment Orders
If the owner or occupier of a hotel or public Building fails to provide, keep in good repair,
alter or improve a means of exit, or fire and life safety equipment required by Part 5 of
this Bylaw, an Officer may issue to the owner or occupier of the hotel or public Building a
written Fire Rescue Department Order requiring that the owner or occupier of the hotel
or public Building take action to meet the requirements of Part 5 of this Bylaw within a
specified period of time.
26.
Evacuation or No Occupancy Order
(1)
The Fire Chief or Fire Prevention Officer may issue a Fire Rescue Department
Evacuation Order in the form shown in Schedule "D" attached to and forming part
of this Bylaw to an owner or occupier of a Building, Structure or area to evacuate
the Building, Structure or area immediately, if the Fire Chief or Fire Prevention
Officer believes there is an imminent and serious danger to life or property of the
occupants or of a panic arising from a fire hazard or risk of explosion.
(2)
The Fire Chief or Fire Prevention Officer may post a notice on any Building,
Structure or area warning that Occupancy of the Building, Structure or area may
be hazardous or that there is "no occupancy" of the Building, Structure or area
due to a fire hazard, and the notice shall be in the form shown in Schedule "C"
attached to and forming part of this Bylaw.
(3)
No person shall remove, alter, or deface any notice posted pursuant to this
Bylaw.
(4)
No person shall remain in a Building or Structure that has been ordered
evacuated or not to be occupied in accordance with an Order under sections
26(1) or 26(2) Fire Rescue Department without prior approval and permission by
the Fire Chief or Fire Prevention Officer.
27.
Fire Protection Technician's Obligations
Fire Protection Technicians when servicing Fire and Life Safety Equipment will:
(a)
notify the Fire Rescue Department prior to any service, test, repair, maintenance,
adjustment, alteration or installation of a sprinkler standpipe or Fire Alarm
System, and prior to any sprinkler standpipe or Fire Alarm Systems or part of
those systems being taken out of service; and
(b)
after any required servicing of Life and Fire Safety Equipment attach to the Life
and Safety Equipment a service tag approved by Fire Chief.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 17
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
28.
Fire Alarm Systems
Contact Persons for Fire Alarm Systems
(1)
An owner or occupier of a Building or Structure at which a Fire Alarm System is
installed shall, on the same day on which the Fire Alarm System becomes
operational, submit to the Fire Rescue Department a list of emergency Contact
Persons in the form shown on Schedule "B" attached to and forming part of this
Bylaw.
(2)
The owner or occupier of a Building or Structure at which a Fire Alarm System is
installed shall inform the Fire Rescue Department of any changes to the
information about the Monitoring Service or Contact Persons by notice in writing
immediately when changes to this information arise.
(3)
The owner or occupier of a Building or Structure at which a Fire Alarm System
has been installed shall ensure that the Contact Persons whose names are
provided pursuant to section 28(2) are persons who are:
(a)
available to receive telephone calls from the Fire Rescue Department or
Monitoring Service in the event that the alarm system at the owner's or
occupier's Building or Structure is activated;
(b)
able to attend at the address of the owner's or occupier's property within
thirty minutes of being requested to do so by the Fire Rescue Department
or Monitoring Service;
(c)
capable of gaining access to the owner's or occupier's Building or
Structure where the Fire Alarm System has been activated; and,
(d)
capable of operating the Fire Alarm System and able to secure the
owner's or occupier's Building or Structure where the Fire Alarm System
has been activated.
(4)
An owner or occupier of any Building or Structure at which a Fire Alarm System
has been installed shall notify the Fire Rescue Department immediately of any
False Alarm incident.
(5)
When a Fire Alarm System has been activated and the owner or occupier of the
Premises at which the Fire Alarm System has been activated or that person's
Contact Person cannot be reached or is unable to attend the Premises, the Fire
Rescue Department will forcibly enter the Building at which the Fire Alarm
System is activated to suppress a fire, or determine the cause of the alarm. The
Fire Rescue Department will secure the Building or provide 24-hour security until
the Building can be secured. The owner or occupier will be charged the fee for
the cost of security or securing the Premises as prescribed in Schedule "A"
attached to and forming part of this Bylaw.
(6)
No owner or occupier of a Building or Structure at which a Fire Alarm System has
been installed shall service, test, repair, adjust, alter or install any parts or items
to the Fire Alarm System that might activate a False Alarm without first notifying
the Fire Rescue Department.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 18
PART 5 - FIRE AND LIFE SAFETY EQUIPMENT AND STANDARDS
28.
Fire Alarm Systems (continued)
Contact Persons for Fire Alarm Systems (continued)
(7)
No owner or occupier of a Building or Structure where a False Alarm has been
activated or that person's Contact Person shall leave the Premises until the
problem that activated the False Alarm is identified and corrected. If the problem
cannot be identified, security by a security company must be placed on site at the
building owner's expense until such time as the problem that activated the False
Alarm is identified and corrected.
PART 6 - BURNING REQUIREMENTS
29.
Open Burning
(1)
Fires and Open Burning set for the purpose of training Members and all fires
located at the Fort St. John Fire Training Centre are exempt from this section of
the Bylaw.
(2)
No person shall ignite any Open Burning fire or cause or permit any Open
Burning fire to be ignited at any time unless the person first obtains a Burning
Permit.
(3)
Where, in the opinion of the Fire Chief, adverse atmospheric conditions do not
permit, or are not conducive to, the ready dissipation of smoke, the Fire Chief
may impose a general ban on all Open Burning for the duration of the said
adverse condition.
(4)
No person shall cause, allow or permit Cooking Fires in any City Park contrary to
a general burning ban.
(5)
No person shall cause, allow or permit any Open Burning in any City Park
contrary to signage banning such Open Burning and without obtaining a Burning
Permit from the Fort St. John Fire Chief.
30.
Burning Permits
(1)
Burning Permits may be issued, cancelled or suspended solely at the discretion
of the Fire Chief or an Officer.
(2)
Burning Permits may be issued for an Open Burning fire:
(a)
by telephone for burning organic yard waste such as garden refuse,
pruning and wood branches on lots that are one (1) acre in size or
greater.
(b)
for stumps and land clearing materials if an air curtain burner is utilized
and with the required Burning Permit.
(c)
for fires smaller than 3.0 meters wide and these fires must be fueled by
hand feeding only.
(d)
for special events in a form prescribed in Schedule "E" attached to and
forming part of this Bylaw.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 19
PART 6 - BURNING REQUIREMENTS
30.
Burning Permits (continued)
(3)
No person who has been issued a Burning Permit for a special event shall ignite
or maintain a fire:
(a)
except on the dates and times permitted on the Permit;
(b)
contrary to the permit conditions.
(4)
No persons shall:
(a)
maintain an Open Burning fire greater than two (2.0) metres in height and
three (3.0) metres wide.
(b)
maintain any Open fire burning greater than three (3.0) metres across in
size unless an Air Curtain Burner or a wood chipper is used.
(c)
locate an Open Burning fire less than three (3.0) metres from any
combustibles.
(5)
No person shall cause, allow or permit open burning of construction materials,
pallets and debris or household garbage.
(6)
Permit requirements shall not apply to outdoor cooking fires which includes
backyard fire pits, provided the fire is contained to a device or fixture designed for
containing the fire and not exceeding 1 metre in diameter. The fire may only
utilize clean, dry wood, or briquettes or propane.
(7)
No person possessing a Burning Permit shall maintain an Open Burning fire
without keeping a competent person at all times in charge of such fire until such
times as the fire is completely extinguished and without providing the competent
person with sufficient equipment in order to prevent the fire from getting out of
control of causing damage or becoming dangerous to life or property.
(8)
Backyard fire pits are required to be a minimum of 4.5 meters from all property
lines and buildings.
31.
Fireworks
(1)
The manufacture, storage, or possession of fireworks exclusively for wholesale
purposes or for the sale of fireworks at wholesale shall conform to the Canada
Explosives Act and Regulations as amended.
(2)
A person may not sell, offer for sale, give, fire or set off low hazard fireworks, as
defined by the Canada Explosives Act within the City of Fort St. John.
(3)
The Fire Rescue Department can display fireworks for civic activities once
the necessary permit is obtained from the fireworks supplier.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 20
PART 7 - FIRE HYDRANTS AND FIRE CONNECTIONS
32.
General Requirements
(1)
The owner of a Private Hydrant must request a City of Fort St. John Hydrant
Identification Number from the Engineering Department and must clearly label
the Private Hydrant with the Identification Number.
(2)
All service work will be identified by the use of the hydrant identification number.
(3)
During construction, servicing or repairs, the owner of a Private Hydrant and
contractors for such owners shall ensure that all fire hydrant conditions affecting
fire safety such as fire hydrants temporarily out of service, low water volumes or
pressures are made known to the Fire Rescue Department immediately.
(4)
All Private Hydrants which are out of service for repair, or not yet in service, must
be wrapped with burlap or black polyethylene plastic sheeting.
(5)
The owner or contractor for the owner of a Private Hydrant must notify the Fire
Rescue and Public Works Departments immediately when a Private Hydrant has
either been taken out of operation or put back into operation.
(6)
No person shall place, leave or allow any vehicle, article, thing or other matter to
interfere with access to or to be located within one (1) metre of a fire hydrant or
fire connection.
(7)
Should any matter or thing be located within one (1) metre of a fire hydrant or fire
connection and is or could cause interference with access to the fire hydrant or
connection, the Fire Rescue Department may cause the matter or thing to be
removed by any Member or Peace Officer or any contractor immediately during
an Incident, or if not during an Incident, within a time specified in an Order in the
form attached as Schedule "C" to this Bylaw and served on the owner or
occupier of the property where the matter or thing is located.
33.
Maintenance & Inspections
(1)
The owner of every Private Hydrant shall have all components of the hydrant
inspected, serviced and tested by a qualified Fire Protection Technician not less
than once a year and the Fire Hydrant Service Report form attached to and
forming part of this Bylaw as Schedule "F" must be submitted to the Fire Rescue
Department within thirty (30) days of the Private Hydrant servicing.
(2)
Records of Private Hydrant inspections and servicing must be kept by the owner
or contractor for three (3) years.
(3)
All fire hydrants in the City of Fort St. John will be painted yellow.
(4)
The owner of a property adjacent to a fire hydrant or on which a Private Hydrant
is located must:
(a)
maintain, clear and keep unobstructed an area having a radius of one (1)
metre around every hydrant;
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 21
PART 7 - FIRE HYDRANTS AND FIRE CONNECTIONS
33.
Maintenance & Inspections (continued)
(b)
keep hydrants clear of ice, snow, shrubs, trees, structures and other
obstructions; and,
(c)
clearly identify their locations.
34.
Service After Each Use
The owner of a Private Hydrant is responsible to conduct or have conducted the
following minimum inspection requirements after each use:
(a)
examine the exterior for broken, cracked or missing parts;
(b)
check to ensure that the hydrant hose ports are the proper elevation and facing a
direction for the most efficient use;
(c)
check to ensure that the hydrant is not obstructed by tall grass, shrubbery or
other items;
(d)
check for worn, rusted or obstructed threads, which may hamper efficient use;
and,
(e)
inspect hydrant barrels to determine if water has accumulated as a result of
leaking main valve, plugged or damaged drain valve.
(f) hydrants used between October 1st - May 1st must have the hydrant barrel
pumped out to prevent freezing.
35.
Semi-Annual Inspection
The owner of a Private Hydrant is responsible to conduct or have conducted the
following minimum inspection requirements semi-annually:
(a)
examine the exterior for broken, cracked or missing parts;
(b)
check to ensure that the hydrant hose ports are the proper elevation and facing a
direction for the most efficient use;
(c)
check to ensure that the hydrant is not obstructed by tall grass, shrubbery or
other items;
(d)
check for worn, rusted or obstructed threads which may hamper efficient use;
(e)
inspect hydrant barrels to determine if water has accumulated as a result of
leaking main valve, plugged or damaged drain valve;
(f)
check for non-drainage of hydrant, leakage past valve seat, plugged drains; and,
(g)
after winter, the hydrant should be checked for damage caused by frost, ground
heave, snow, road salt or sand.
36.
Annual Servicing
The owner of a Private Hydrant is responsible to conduct or have conducted the
following minimum inspection requirements annually:
(a)
hydrants shall be flushed with main valve and outlet valves fully open until the
water runs clear of any visible debris; and,
(b)
check the operation of the main line valve by closing the isolating valve.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 22
37.
Three Year Servicing
The owner of a Private Hydrant is responsible to conduct or have conducted the
following inspection every three (3) years:
(a)
disassemble the hydrant and check for worn or broken parts and leaks;
(b)
lubricate all external and internal working parts during reassembly;
(c)
check water pressure; and,
(d)
reopen main line valve and check to see if hydrant operates and close hydrant
valve.
PART 8 - STREET ADDRESSES
38.
Civic Street Numbers
(1)
An owner or occupier of a Building or Structure must ensure that the civic
address for the property at which the Building or Structure is located is posted so
as to be clearly visible from the road using numbers that shall be a minimum of
7.63 millimeters (3 inches) in height and of a colour that contrasts with a surface
on which they are mounted.
(2)
The owner or occupier of a commercial or multi-residential use property shall
ensure that the unit number for each individual unit within a commercial or multi-
residential use property are posted in a visible location at the entry to each unit,
are a minimum of 76.3 millimetres (3 inches) in height and of a colour that
contrasts with the surface on which they are mounted.
(3)
The owner or occupier of a multi-residential complex shall post a site plan at the
main driveway entry to the complex which shall be clearly visible upon entry to
the complex and indicate the number of each unit and the location of access to
each unit within the complex.
PART 9 - INTERPRETATION AND PENALTIES
39.
Schedules
The schedules in this Bylaw form part of this Bylaw and are enforceable in the same
manner as this Bylaw.
40.
Severability
In the event that any portion of this Bylaw is declared ultra vires by a Court of competent
jurisdiction, then such portion shall be deemed to be severed from the Bylaw with the
intent that the remainder of the Bylaw shall continue in full force and effect.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 23
PART 9 - INTERPRETATION AND PENALTIES
41.
Penalties and Enforcement
1.
Any person who contravenes any provision of this Bylaw is liable to the City for
and must indemnify the City from all costs, expenses, damages and injuries
resulting from the contravention. This does not in any way limit any other
provision or any other remedy the City may have under this Bylaw or otherwise at
law.
2.
Every person who violates any of the provisions of this Bylaw, or who suffers or
permits any act or thing to be done in contravention of this Bylaw, or who
refuses, omits, or neglects to fulfill, observe, carry out, or perform any duty or
obligation imposed by this bylaw is liable to a fine of not less than the sum of Fifty
Dollars ($50.00) but not exceeding the sum of Ten Thousand Dollars ($10,000).
3.
The minimum and maximum fines for breach of this bylaw pursuant to the
Offence Act and Section 263 of the Community Charter are those listed in
Schedule "H".
4.
Where there is an offence that continues for more than one day, separate fines
may be issued for each day or part thereof in respect of which the offence occurs
or continues.
5.
Nothing in this Bylaw limits the City from utilizing any other remedy that is
otherwise available to the City at law.
6.
The City designates this Bylaw as a bylaw that may be enforced by means of a
ticket in the form prescribed for that purpose by the Community Charter and the
Community Charter Bylaw Enforcement Ticket Regulation.
7.
The persons who are appointed to the job positions or titles listed below are
designated as Bylaw Enforcement Officers for the purposes of issuing tickets
under this Bylaw:
-
Fire Chief,
-
Deputy Fire Chief,
-
Fire Inspector,
-
Captain,
-
Lieutenant,
-
Fire Prevention Officer,
-
RCMP Members,
-
Bylaw Enforcement Officers.
8.
The words or expressions set forth in Column 1 of Schedule "H" of this Bylaw
designate the offence committed under the Bylaw section number appearing in
Column 2 opposite the respective words or expressions for the purposes of
issuing tickets under the Community Charter.
9.
The amounts appearing in Column 3 of Schedule "H" of this bylaw are the fines
set pursuant to the Community Charter of the corresponding offences designated
in Column 1 for the purposes of issuing tickets under the Community Charter.
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 24
42.
Repeal
The "Fire Prevention and Regulation Bylaw No. 1326, 1998" is hereby repealed.
READ FOR A FIRST TIME THIS
26th
DAY OF
November,
2012
READ FOR A SECOND TIME THIS 11th
DAY OF
March,
2013
READ FOR A THIRD TIME THIS
11th
DAY OF
March,
2013
ADOPTED THIS
25th
DAY OF
March,
2013
LORI ACKERMAN
JANET PRESTLEY, DIRECTOR OF
MAYOR
LEGISLATIVE AND ADMINISTRATIVE
SERVICES
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 25
SCHEDULE A
FEES
Section
Description
Fee in Dollars ($)
10(a)
File Searches
150.00 per file
10(b)
Special Property Inspection
100.00
10(c)
Fire Extinguisher Course Fee - Per Participant
15.00
10(d)
Request Building, Structure Re-Inspection Fee
100.00
10(g) and
30.4(b)
Burning Permit for fires larger than two metres high x
three metres wide with an air curtain
50.00
10(g) and 30
Burning Permit
50.00
10(h)
Fuel Tank Installation/Removal/Repair/Upgrade
Permit
100.00
10(h)
Above Ground Fuel Tank Permit under 25,000 litres
200.00
10(h)
Above ground Fuel Tank Permit over 25,000 litres
.002 cents per litre
10(h)
Below Ground Fuel Tank Permit under 5,000 litres
100.00
10(h)
Below ground Fuel Tank Permit between 5,001 and
25,000 litres
250.00
10(h)
Below ground Fuel Tank Permit between 25,001 and
50,000 litres
350.00
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 26
SCHEDULE B
EMERGENCY CONTACT PERSON FORM
Please print clearly:
Owner Name:
__________________________________________________________
Occupier Name (if any):
__________________________________________________
Address of Premises with Fire Alarm System:
_________________________________
Owner Telephone Number:
________________________________________________
Occupier Telephone Number (if any):
________________________________________
First Emergency Contact Person Name:
______________________________________
Relation to Owner or Occupier:
_____________________________________________
Emergency Telephone Number:
____________________________________________
Second Emergency Contact Person Name:
___________________________________
Relation to Owner or Occupier:
_____________________________________________
Emergency Telephone Number:
____________________________________________
Third Emergency Contact Person Name:
_____________________________________
Relation to Owner or Occupier:
_____________________________________________
Emergency Telephone Number:
____________________________________________
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 27
SCHEDULE C
ORDER FORM
FORT ST. JOHN FIRE RESCUE DEPARTMENT ORDER
TO
Having inspected the Premises __________________________________ by you to
with: ________________
located at _____________________________, British Columbia
and legally described as
_______________________________________ (the "Premises"),
on the _______ day of _______, _____
(Day)
(Month)
(Year)
I, ____________________, being the Fire Chief or a Fire Prevention Officer with the Fort St.
John
(Name of Officer)
Fire Rescue Department FIND THAT:
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
_____________________
THEREFORE, pursuant to the authority vested in me and under the "Fire Protection and Life
Safety Regulation Bylaw No. 2106, 2012" you are HEREBY ORDERED TO:
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
The action or work specified in this Order must be completed within ______ days after receipt of
this Order. Should any requirement of this Order not be carried out or completed within the time
prescribed, a $100.00 fee shall be billed to the Owner or Occupier for any subsequent
inspection required.
Owner or Occupier Name: ____________________________________________
Fire Chief or Fire Prevention Officer: ____________________________________
I, Served a copy of this Order on ______________________ at ____________________,
(Owner or Occupier)
(Location)
BRITISH COLUMBIA on ________________.
(Date)
Signed:____________________________
Signed:______________________________
Fire Prevention Officer
Owner or Occupier acknowledging
receipt of Order
(owned or occupied)
(type of occupancy)
(civic address)
(legal description)
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 28
SCHEDULE D
EVACUATION ORDER
Evacuation Order
By Order of the Fort St. John Fire Rescue Department
The building located at _____________________________________________, Fort St. John,
British Columbia
(Civic Address)
and legally described as ______________________________________, (the "Premises") is
ordered to be evacuated under the City of Fort St. John Fire Protection and Life Safety
Regulation Bylaw No. 2106, 2012 Section 26.1.
____________________________________________________________________________
(Reason for Evacuation)
NO PERSON shall enter this building without the authorization of the Fire Chief.
Date of Posting _______________________________
No person shall remove, alter or deface or cause to be removed altered or defaced, this notice
as per Section 26.3 of the City of Fort St. John Fire Protection and Life Safety Regulation Bylaw
No. 2106, 2012.
Order posted at the Premises on:
______________________________
__________________________
Fire Chief or Fire Prevention Officer
(Date)
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 29
SCHEDULE E
BURNING PERMIT
Burning Permit $50.00
Special Event Burning Permit
Other
Organic Waste
Open Burning of Stumps/Land Clearing (air curtain burner)
Date: _____________, Authority granted to:__________________Phone:____________
Fire Location and Event: _________________
Ceremonial Training by: _________________ Tribal Name: ______________________
Number of Fires: _______ Permit valid Inclusive From: _______________ to:________________
Subject to the following conditions:
The Permit Holder shall be responsible for the fire/s authorized by this permit and shall during light-up
and for the duration of the fire, undertake the following:
-
Provide one adult person equipped with a garden hose connected to a water source and shovel
suitable to effectively safeguard the fire.
-
Shall insure the safeguarding forces to extinguish the fire/s authorized by this permit until the fire/s
have been completely extinguished.
-
Shall not start or rekindle fire/s during windy weather and shall take such extra precautions as are
necessary to prevent fire from escaping during windy periods.
-
Shall totally extinguish all fires authorized by this permit on or prior to the expiry date of this
permit: or shall extinguish them forthwith upon suspension or cancellation of the permit; or when
instructed to do so by the Fire Chief or designate.
-
Shall not allow burning to continue, where that burning, in the opinion of the Fire Chief, is a
nuisance because of the emission of smoke and ash.
-
Shall be responsible for all costs incurred to suppress any fire that escapes or threatens to
escape from burning or that causes a nuisance because of smoke or ash.
-
In the event of the Permit Holder failing to suppress any fire to the satisfaction of the Fire Chief,
the Fire Chief may cause such fire/s to be immediately suppressed.
-
It is prohibited to burn rubber tires, tar, asphalt shingles, or any other like substances, which
produce heavy black smoke on or in any fire authorized by this permit.
-
This permit is subject to cancellation or suspension at any time at the discretion of the Fire Chief
or an Officer of Fort St. John Fire Rescue Department where there is a violation of any condition
under which the permit was issued.
I have read and understand the conditions of this burning Permit.
Permit Holder _______________________________________ (Signature)
Issued By ______________________________ Title _________________________
Fort St. John Fire Rescue Department
("Hereinafter the Permittee")
("Elder's Name")
("Date & Time")
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 30
SCHEDULE F
PRIVATE FIRE HYDRANT SERVICE REPORT
Hydrant Service Report
Fire Protection Technician:
________________________________________________
Owner:
_______________________________________________________________
Hydrant No.: __________________
Test Date: ___________________________
Location:
______________________________________________________________
Main Size: _____________ Flow Rate: ____________ Ports: _____________
Out of Service:
Yes
No
Comments: __________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
Pressure: _________ Make: __________________Distance to isolation valve: _______
Branch valve operated:
Yes
No
Service top end:
Yes
No
Serviced bottom end:
Yes
No
Service threads:
Yes
No
Flushed out:
Yes
No
Pressure tested:
Yes
No
Greased:
Yes
No
Drains properly:
Yes
No
Painted:
Yes
No
Weed eaten:
Yes
No
Comments: __________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
Further work recommendation: ___________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 31
SCHEDULE G
APPLICATION TO REMOVE AND/OR INSTALL A FUEL STORAGE TANK AND PIPING
COMMERCIAL PROPERTY
1. Fill out application form and fax or deliver to the Fire & Loss Prevention Division of Fort St.
John Fire Rescue.
2. The Fire & Loss Prevention Division will process application within seven (7) business days
and will contact the applicant to arrange for pick-up of the permit(s).
3. Applicant will pay for permit(s) at the time of issue.
4. On-site inspection is required during tank removal by the Fire Rescue Department.
Permit Costs:
Permit for Underground Fuel Storage Tank Removal per Tank = $100.00
Permit for the Installation of Above Ground Fuel Storage Tanks: 2,500 Litres (550 Gallons)
to 25,000 Litres (6640 Gallons) = $200.00, Each Litre over 25,000 = .002cents per litre
Permit for the Installation of Below Ground Fuel Storage Tanks -up to 5,000 Litres =
$100.00, up to 25,000 Litres = $250.00, Up to 50,000 Litres = $350.00
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 32
SCHEDULE G
APPLICATION TO REMOVE, INSTALL, REPAIR OR UPGRADE FUEL STORAGE TANK
AND/OR PIPING FOR COMMERCIAL PROPERTY
The applicant hereby applies for permission to (check all that apply):
Remove
Install
Repair
Upgrade
Number of Tanks to be removed:
Number of Tanks to be installed, repaired or upgraded (in litres):
Tank and Piping
Tank Only
Above Ground
Underground
Piping Only
Tank Only
In accordance with the particulars and plans submitted herewith, it is understood that
completion of this form constitutes an application only and that the work applied for will not be
commenced until a permit to install and/or remove has been issued.
Civic Address:
Full Name of Registered Owner:
Mailing Address of Registered Owner:
Name of Contractor/Installer:
Address of Contractor:
__________________________________________________________
Phone Number of Contractor:
____________________________________________________
Name of Applicant (if different):
City of Fort St. John - Planning Department
Date Application Received:
Approved:
YES
or
NO
Comments:
Signature:
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 33
SCHEDULE H
MUNICIPAL TICKET INFORMATION PENALTIES
COLUMN 1
OFFENCE
COLUMN 2
SECTION
COLUMN 3
FINE
Non-compliance with Fire Rescue Department
Order
10(d)
100.00
False Alarm Fee
10(f)
False Alarm Bylaw
No. 1615, 2003
Drive over fire hose
13(1)
200.00
Failure to assist
13(2)
250.00
Failure to obey evacuation order
13(3)
250.00
Failure to secure a premise after fire
13(5)
200.00
Failure to comply with direction
13(8)
250.00
Interfere with fire equipment
13(9)
250.00
Building in state of disrepair
14(1)(a)
200.00
Endanger life or property
14(1)(b)
200.00
Allow flammable conditions
14(1)(c)
200.00
Allow a fire hazard to exist
14(1)(d)
250.00
Failure to repair
14(2)(a)
200.00
Failure to remove or destroy
14(2)(b)
200.00
Failure to alter the use or occupancy
14(2)(c)
200.00
Failure to remove combustible or explosive
materials
14(2)(d)
200.00
Failure to remove or take precautions against an
identified fire hazard
14(2)(e)
200.00
Failure to adopt and/or practice fire drill for
owner/occupier of hotel, hospital community care
facility or other building with sleeping
accommodation and used for the care of persons
16(1)
200.00
Failure to adopt and/or practice fire drill for
owner/occupier of a school, child care facility,
children's home or other institution for children's
education or care
16(2)
200.00
Failure to submit Fire Safety Plan
17(1)
200.00
Failure to resubmit updated Fire Safety Plan
17(2)
200.00
Failure to publicly post notice of Fire Safety Plan
to occupants residing in the building or structure
17(3)
200.00
Failure to submit Pre-Incident Plan
18(1)
200.00
Failure to submit updated Pre-Incident Plan
18(2)
200.00
Failure to install smoke alarm(s), sprinklers or fire
alarm(s)
19(1)
200.00
Failure to store combustible materials in proper
container
20(1)
200.00
Container containing combustible materials
without a lid
20(2)
200.00
Storing combustible refuse containers within 10
feet of building or fuel tank
20(3)
200.00
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 34
SCHEDULE H
MUNICIPAL TICKET INFORMATION PENALTIES
COLUMN 1
OFFENCE
COLUMN 2
SECTION
COLUMN 3
FINE
Failure to supply proper non-combustible
container for spontaneous combustion products
21(1)
200.00
Failure to close lids on non-combustible container
21(2)
200.00
Improper storage of flammable or combustible
liquids or products contrary to Fire Code
21(3)
200.00
Failure to submit Declaration of on Site
Chemicals and Hazardous Materials Form
21(4)
200.00
Failure to obtain fuel storage tank permit
22(1)
250.00
Failure to keep smoke and fire doors closed
23(1)
200.00
Altering church, hotel or public building exit
door(s) without approval
23(2)
200.00
Install locking device on exit doors without
approval
23(3)
200.00
Install a fire lane access gate without approval
24(1)
200.00
Blockage of primary or secondary vehicular
access without approval
24(2)
200.00
Failure to post exit signs
24(3)
200.00
Failure to post exit plan
24(4)
200.00
Failure to illuminate exit sign
24(5)
200.00
Interfere with egress or access
24(6)
200.00
Failure to tag Life and Fire Safety Equipment
25
200.00
Alter or deface evacuation or no occupancy order
notice posted
26(3)
200.00
Failure to evacuate
26(4)
250.00
Failure to notify before
servicing/testing/replacing/installing Fire Alarm
System
27(1)(a)
200.00
Failure to supply contact person information for
fire alarm system
28(1)
200.00
Failure to notify changes to information for fire
alarm system
28(2)
200.00
Failure to ensure that Contact Person is able to
respond to incident when contacted
28(3)
200.00
Failure to notify Fire Rescue Department of false
alarm
28(4)
200.00
False Alarm Entry Where No Contact Person is
available
28(5)
300.00
Failure to notify Fire Rescue Department prior to
servicing
28(6)
200.00
Failure to remedy false alarms
28(7)
250.00
Open burning fire without burning permit
29(2)
200.00
Burning contrary to general fire ban
29(3)
200.00
Cooking fires in City Park contrary to a general
burning ban
29(4)
200.00
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 35
SCHEDULE H
MUNICIPAL TICKET INFORMATION PENALTIES
COLUMN 1
OFFENCE
COLUMN 2
SECTION
COLUMN 3
FINE
Open burning fire in City Park without burning
permit
29(5)
200.00
Open burning outside permitted times
30(3)
200.00
Emission of offensive smoke or ash
30(5)
200.00
Fire too large
30(4)(a)
200.00
Fire too close to combustibles
30(4)(b)
200.00
Fire fuel not hand fed
30(4)(c)
200.00
Burning prohibited materials
30(5)
200.00
Fire Unattended
30(7)
200.00
Failure to mark ID on hydrant
32(1)
200.00
Set off fireworks in contravention
31(2)
100.00
Failure to notify before servicing or repairing
private hydrant
32(3)
200.00
Failure to cover inoperable private hydrants
32(4)
200.00
Failure to notify when hydrant non-operational
32(5)
200.00
Interfere with access to hydrant
32(6)
200.00
Failure to submit Fire Hydrant Service Report
33(1)
200.00
Failure to keep private hydrant inspection and
servicing records
33(2)
200.00
Hydrant not correct colors
33(3)
200.00
Failure to keep hydrant unobstructed
33(4)
200.00
Failure to follow private hydrant service
requirements
34
250.00
Failure to conduct private hydrant semi-annual
inspection
35
250.00
Failure to conduct private hydrant annual
inspection
36
250.00
Failure to conduct private hydrant three year
service
37
250.00
Failure to post civic address on building or
structure
38(1)
200.00
Failure to post unit number on building or
structure
38(2)
200.00
Failure to post site plan at main driveway
entrance
38(3)
200.00
City of Fort St. John Fire Prevention Bylaw No. 2106, 2012
Page 36
SCHEDULE I
DECLARATION OF ON SITE CHEMICALS AND HAZARDOUS MATERIALS
To be submitted as part of occupancy process (for properties in C3, C4, C5, M1 and M2 zones)
for review by the Fire Department. Approval in writing from the Fire Department will be required
before chemicals and/or hazardous materials can be stored on site. A material safety data sheet
(MSDS) must be attached for all products listed below.
The materials declared on this form must be properly contained in a manner acceptable to the
Fire Department and must be in full compliance with ALL applicable legislation.
Product Name
Quantity
Hazardous Class
(as per MSDS)
Declaration:
I hereby make application for declaration of on-site chemicals and/or hazardous materials in
accordance with the particulars as above stated and declare the information is true and correct.
I undertake that if I am granted approval for this application that I will comply with each and
every obligation contained in all laws and Bylaws now in force or which may come into force in
the City of Fort St. John. I further understand that if this application involves the use of the
premises for business purposes that they may not be occupied until they have been inspected
by the Department concerned and approval has been granted. By signing this application I
agree to these terms.
Owner/ Agent Signature: _________________________________ Date: __________________
Owner/ Agent Printed Name: ____________________________ Phone: (_____) ___________
Address of Subject Property: _____________________________________________________
For Office Use Only:
Fire Department Approval: ________________________________ __________________________
Signature
Printed Name