THE CORPORATION OF THE TOWN OF BANCROFT
BY-LAW NO. 67-2016
Being a By-law to adopt a policy to regulate Cross
Connection and Backflow Prevention on plumbing
systems as required in order to protect the Town of
Bancroft's Drinking Water Supply and Distribution System
from Contamination.
WHEREAS Section 11 of the Municipal Act 2001, c.25, as amended, provides that
lower-tier municipalities may pas by-laws respecting matters within the public
utilities sphere of jurisdiction;
AND WHEREAS under Section 130 of the Municipal Act 2001, c. 25, as amended,
a municipality may regulate matters not specifically provided for by the Act or any
other Act for purposes related to the health, safety, and well-being of the inhabitants
of the municipality;
AND WHEREAS Part III of the Act under the heading "Public Utilities" provides for
specific municipal powers within the public utilities sphere of jurisdiction;
AND WHEREAS Section 11 of the Safe Drinking Water Act requires that
municipalities ensure that their respective drinking water system meets prescribed
drinking water standards to the point where the system is connected to a user's
plumbing system;
AND WHEREAS Part 7 of the Ontario Building Code requires potable water
systems to be protected from contamination, but limited to specific building uses;
AND WHEREAS the Municipal Act 2001, c. 25, as amended, allows a municipality
to delegate its authority to impose fees and charges on persons for services or
activities provided or done by or on behalf of it, to provide for inspections and
inspection orders, and to make orders to discontinue activity or to do work;
AND WHEREAS the Town of Bancroft has deemed it expedient to put into place
regulations for Cross Connection and Backflow Prevention on plumbing systems as
required to protect the Town of Bancroft's Drinking Water Supply and Distribution
System from contamination;
NOW THEREFORE THE COUNCIL OF THE CORPORATION OF THE TOWN OF
BANCROFT HEREBY ENACTS AS FOLLOWS:
1. THAT the Town of Bancroft Cross Connection and Backflow Prevention
Policy, attached as Schedule "A" to this by-law, is hereby approved.
2. THAT Mayor and Clerk be and are hereby authorized to sign this By-Law and
affix the corporate seal thereto.
3. THAT this By-Law is enacted upon the third and final reading hereof.
Read a first, second and third time, and be finally passed, signed, sealed and
numbered By-Law 67-2016, this the 13th day of September, 2016.
Original Signed in File
BERNICE JENKINS, MAYOR
Original Signed in File
HAZEL LAMBE, CLERK
2
Schedule "A" to By-Law 67-2016
TOWN OF BANCROFT
CROSS CONNECTION AND BACKFLOW PREVENTION POLICY
1. Definitions
1.1 "ASSE" means the American Society of Sanitary Engineering;
1.2 "AWWA" means the American Water Works Association;
1.3 "auxiliary water supply" means any water supply on or available to the premises
other than the Town's approved public water supply;
1.4 "authorized functions list" means the list of functions and the persons authorized to
carry out such functions as set out in Schedule "A" of this by-law;
1.5 "backflow" means the flowing back or reversal of the normal direction of flow of
water;
1.6 "backflow prevention device'' means a device that prevents backflow, certified to the
CAN/CSA Standard
1.7 "building" shall have the same meaning as set out in the Building Code Act, S.O.
1992, c23, as amended, or any successor thereof;
1.8 "building code" means regulations made under Section 34 of the Building Code Act,
as amended or re-enacted from time to time;
1.9 "Chief Building Official" means the Chief Building Official appointed by the Town of
Bancroft under Section 3 of the Act;
1.10
"commercial" means the use of land, building or structure for the purpose of
buying, selling, leasing and renting commodities or accommodations, and/or
supplying of services as distinguished from such uses as manufacturing or
assembling of goods, warehousing, transport terminals, construction and other
similar uses;
1.11
"cross-connection" means any actual or potential connection between a
potable water supply or system and any source of pollution or contamination and
includes any by-pass, jumper connection, removable section of pipe, swivel or
changeover device and any other temporary or permanent connection arrangement
through which backflow may occur;
1.12
"cross-connection survey" means a complete review of the potable water
system or systems on the premises to determine if any cross connection exists and
includes existing backflow prevention devices, cross-connections discovered,
corrective measures and recommendations submitted on the Town's standard
cross-connection inspection report form;
1.13
"CSA Standard" means the document entitled CAN/CSA-B64.10-
11/CAN/CSA-B64.10.1- 11 - Manual for the Selection and Installation of Backflow
Prevention Devices/Manual for the Maintenance and Field Testing of Backflow
Prevention Devices including all appendices published by the Canadian Standards
Association, or any successor thereof;
1.14
"enclosure" means an above ground structure, certified to ASSE Standard
1060 for Outdoor Enclosures for Backflow Prevention Assemblies, designed to
accommodate a backflow prevention device, which incorporates positive drainage to
prevent submergence of the backflow prevention device, provides security,
increases accessibility for testing and repair, and provides freeze protection;
1.15
"fire protection system" means any system within a Building or Structure for
the suppression of a fire, including but not limited to any system consisting of a
water sprinkler system or dry foam, or a system described in the CSA Standard;
3
1.16
"hazard" means one of three levels of hazard: minor, moderate and severe
as defined by CAN/CSA B64.10;
1.17
"industrial" means premises used for warehousing of goods and materials,
the assembly of manufactured goods, the manufacturing of goods, the repair and
servicing of goods and similar uses;
1.18
"institutional" means a use that caters to the social, educational or religious
needs of humans including places of worship, schools, senior's residences,
hospitals, recreation centers, libraries or municipal / provincial /federal offices, etc.;
1.19
"multi-residential" means a dwelling unit in a building containing four or more
dwelling units, each of which has an independent entrance directly from the outside
or through a common vestibule or common corridor;
1.20
"municipal law enforcement officer" means a property standards officer who
has been assigned the responsibility of administering and enforcing by-laws under
section 15.1 of the Building Code Act 1992;
1.21
"occupant" means any lessee, tenant, owner, the agent of a lessee, tenant or
owner, or any person in possession of or occupying a property;
1.22
"person" includes a corporation and their heirs, executors, administrators,
successors, or other legal representatives of a person to whom the context can
apply according to law;
1.23
"owner" means any person, firm or corporation having control over property
to which this by-law applies and includes the owner registered on the title of the
property and any occupant of any building located on such property;
1.24
"plumbing" means plumbing as defined in the Building Code Act and includes
a private water main, a water service extension and a plumbing system but does not
include the water system;
1.25
"plumbing system" means the system of connected piping, fittings, valves,
equipment, fixtures and appurtenances contained in plumbing and connected to the
water meter or a water service pipe that conveys water to water supply outlets,
fixtures, plumbing fixtures and devices from immediately after the curb stop;
1.26
"potable water" means water that is safe for human consumption;
1.27
"premises" means any house, tenement, building, lot, or part of a lot, or both,
in, through, or past which water service pipes run;
1.28
"premise isolation" means separation of the plumbing system within a
building or structure from the Town's water distribution system;
1.29
"property" means each separately assessed parcel of land connected to the
water system or fronting on the water system and includes a condominium unit in a
condominium corporation and the common elements in a condominium corporation;
1.30
"property isolation" means isolation of a property from the Town's water
distribution system immediately after the curb stop;
1.31
"qualified person" means a person with approved qualifications set out in
schedule "A" of this by-law;
1.32
"residential" means the use of land, buildings or structures for human
habitation, but excluding temporary human habitation uses such as short term
accommodation, bed and breakfast establishment, tourist cabin or cottage , hotel or
motel;
1.33
"tester's certificate" means a current Cross Connection Control Specialist
certificate issued by a participating Canadian section of the AWWA;
1.34
"Town" means the Corporation of the Town of Bancroft and includes its
employees, servants and agents;
1.35
"water distribution system" means the water system and the plumbing
including a plumbing system;
1.36
"water service connection" means a piping connection that conveys water
from the water distribution system to the plumbing system".
2. Application, interpretation and administration of by-law
2.1 This By-law applies to existing buildings, buildings subsequent to occupancy and future
industrial, commercial, institutional, multi-residential and residential buildings and
structures and in-ground irrigation systems.
4
2.2 In addition to and notwithstanding Part 2.1 of this By-law, this By-law applies where a
condition exists in any building or structure that may be hazardous or detrimental to the
potable water supply as determined by the Town of Bancroft.
2.3 In the event of conflict between the provisions of this By-law and the provisions of any
other statute, regulation or by-law, the provisions that are the most restrictive prevail.
2.4 The following Schedules are attached to and form part of this By-Law:
Schedule A: Authorized Functions List
Schedule B: Town of Bancroft Registration Requirements for Persons on Authorized
Functions List
2.5 This By-law shall be administered jointly on behalf of the Town by the Manager of Public
Works and Chief Building Official and/or By-Law Enforcement Officer, unless another
Town official is specifically referred to in this By-law. Where under the terms of this By-
law decisions, approvals, notices and certificates are to be made, given or issued by the
Town, such decisions, approvals, notices and certificates shall be made, given or issued
by the Manager of Public Works and Chief Building Official and/or By-law Enforcement
Officer or other named Town official.
3. Protection from contamination and backflow prevention
3.1 No person shall connect, cause to be connected, or allow to remain connected to the
plumbing system or water distribution system any piping, fixture, fitting, container or
appliance, in a manner which under any circumstances may allow untreated water,
wastewater, any source of pollution or any other liquid, chemical or substance to enter
the water plumbing system or water distribution system. The means for "protection from
contamination" shall be in accordance with the requirements of the Building Code Act,
as amended.
3.2 Premises isolation shall be provided for all buildings within the Town of Bancroft in
addition to any plumbing or building code requirements for individual or zone protection
because backflow into the water system can still occur if the individual protection fails.
At the discretion of the Town of Bancroft, alternative methods may be utilized to ensure
protection of the potable water supply.
3.3 Backflow Preventer Standards
3.3.1 The selection, installation, maintenance, and field testing of backflow preventers
must follow the CAN/CSA B64.10 Standard (CSA, November 2011 or latest
amendment). All approved backflow preventers must conform to the following, and
shall be certified by the CSA or a certification body recognized by the Standards
Council of Canada:
a) CAN/CSA-B64 SERIES-11 Backflow Preventers and Vacuum Breakers
which comprises B64.0, B64.1.1, B64.1.2, B64.2, B64.2.1, B64.2.2, B64.3,
B64.3.1, B64.4, B64.4.1, B64.5, B64.5.1, B64.6, B64.6.1, B64.7, B64.8,
B64.9; and,
b) ASME A112.18.1/CAN/CSA-B125-01 or CSA-B125.3 Plumbing Fittings; and,
c) The Ontario Building Code.
4. Cross connection inspection reports
4.1 Inspection Reports
The owner(s) responsible for any buildings billed for water for an Institutional,
Commercial, Industrial, high density residential use building or having in-ground
irrigation systems, shall retain a Qualified Person as indicated in Part 13 to prepare a
Cross Connection Inspection Report in the form prescribed by the Town.
4.2 Access to Auxiliary Supply
Notwithstanding Part 2.1, owners of residential buildings within the scope of Part 9 of
the Ontario Building Code that have access to an auxiliary water supply shall, every five
5
(5) years or upon request, provide the Director with a Cross Connection Inspection
Report completed by a qualified person.
4.3 Inspection Report - Submission Date
The Cross Connection Inspection Report shall be submitted to the Town before the date
stated in Part 9. The Cross Connection Inspection Report shall include existing backflow
prevention devices, cross connections discovered, corrective measures,
recommendations and a schedule of work to be completed. The method of cross
connection control or selection and installation of backflow prevention devices shall be
in accordance with the Ontario Building Code. In the case of premises with access to an
auxiliary water supply, a written confirmation by a qualified person stating that a physical
separation exists is an approved alternative to a backflow prevention device.
4.4 Access - Reasonable Notice
Notwithstanding the obligations for persons to undertake a Cross Connection Inspection
Report, the Director shall be allowed access, with reasonable notice, to any premises
that are connected to the water distribution system for the purpose of performing
inspections to locate possible cross connections. The Director may require a routine
cross connection inspection of the premises (at the owner's expense) to be performed
by a qualified person.
4.5 Access Not Provided
Where access is not provided, a written notice by the Director may be issued providing
the time frame to allow access. If access is not provided within this time frame, the
Director may, at their discretion, shut off the supply of water to the premises until such
time as access is provided.
4.6 Compliance Notice
If a condition is found to exist which is contrary to Part 3 of this By-law, the Director may
issue such notices to the person and take actions as the case may be, as may be
required to obtain compliance with these regulations, including shutting off the supply of
water to the premises until such time as compliance is obtained.
5. Premise Isolation
5.1 Where, in the opinion of the Director, a risk of possible contamination of the water
distribution system exists, a person on notice from the Director shall install premise
isolation within the building or complete property isolation in an ASSE 1060 certified
enclosure on the property line in addition to any other source of protection devices on
the premises.
5.2 Premise isolation shall be installed: (a) in buildings of moderate or severe hazard in
accordance with premise isolation requirements as stated in the Ontario Building Code
Part 7 Plumbing; or (b) as specified by the Director based on Part 3 of this By-law.
5.3 Three levels of protection shall be recognized for premises isolation, according to the
hazard ratings as in CSA B64.10, as follows: (a) Premises with a minor hazard
classification shall be isolated with a Dual Check Valve (DuC) backflow preventer. (b)
Premises with a moderate hazard classification shall be isolated with a Double Check
Valve Assembly (DCVA) backflow preventer. (c) Premises with a severe hazard
classification shall be isolated with a Reduced Pressure Principle (RP) backflow
preventer.
5.4 Where, in the opinion of the Town, a risk of possible contamination of the water
distribution system may exist, the owner shall have an approved backflow prevention
device installed and tested by a qualified person(s).
6. Cross Connection Compliance (Including Premise Isolation)
6.1 Town staff shall review the submitted Cross Connection Inspection Reports specified in
Part 4 and issue a 'Compliance Notice' that may support the recommendations
6
contained in the Cross Connection Inspection Report. The 'Compliance Notice' may
contain additional or alternative requirements deemed necessary by the Town in
accordance with the provisions of this By-law.
6.2 If work is required, the owner receiving the 'Compliance Notice' shall retain a qualified
person(s) to undertake the stated works before the date stated in the 'Compliance
Notice' and advise the Town, in writing, of completion of the work within thirty(30) days
of the date stated.
6.3 If the owner to whom the Town has issued a Notice fails to comply with the 'Compliance
Notice', the Director, at their discretion, may:
(a) Instruct the owner to correct the fault at their expense within a specified time
period and if the Notice is not complied with, the Town may then shut off the water
service or services; and/or
(b) Request that the Chief Building Official consider issuing an unsafe order under
unsafe requirements in accordance with the Ontario Building Code Act, in a
condition that could be hazardous to the health or safety of persons in the normal
use of the building, persons outside the building or persons whose access to the
building has not been reasonably prevented; and/or
(c) Without notice to the owner, shut off water service, where the Town has
determined, in their sole discretion that an immediate threat of contamination to the
water system exists that may endanger public safety or health.
7. Maintenance and Field-Testing of Backflow Prevention Devices
7.1 The owner responsible for properties, premises or buildings containing backflow
prevention devices shall retain a qualified person, per Part 12, to annually inspect and
test, at the expense of the owner, and submit a Backflow Device Test Report on a form
prescribed by the Director to demonstrate that the device is in good working condition.
All equipment used to test backflow preventers shall be verified or calibrated for
accuracy, as described in CAN/CSA B64.10.
7.2 If the results of a test show that a back flow prevention device is not in good working
condition, the owner shall make repairs or replace the device within five (5) working
days.
7.3 If an owner does not make the appropriate repairs or replace the defective device within
the five (5) working days, the Director may shut the water service or services off.
7.4 If the owner fails to have a backflow prevention device tested, the Director may notify
the owner that the back flow prevention device must be tested within a specified time.
7.5 If an owner fails to have a backflow prevention device tested within the specified time of
the notice, when requested by the Director, the Director may shut off the water service
or water services until the backflow prevention device has been tested and approved.
8. Removal of Backflow Prevention Devices Prohibited
8.1 No person shall remove a backflow prevention device or part thereof after it has been
installed, and no owner of a building or structure in which a backflow prevention device
is installed shall cause or permit the removal of such device, unless such removal is:
(a) To facilitate the repair of the device and such device is replaced immediately
after such repair is carried out; or
(b) To replace the device with another device that meets or exceeds the provisions
of this By-law. In no instance shall the property, premise or building be without a
backflow prevention device for more than five (5) days.
9. Inspection Report, Implementation and Retesting Schedule
9.1 The requirements under this regulation shall be undertaken as follows:
(a) Municipal Water Service Accounts (Institutional, Commercial, Industrial and
Multi-Residential Buildings)
7
(i) Submission of Cross Connection Inspection Report; within six months of
the date of contact by the Manager of Public Works or Chief Building Official
and/or Bylaw Enforcement Officer.
(ii) Implementation of Report recommendations as determined by the
Manager of Public Works or Chief Building Official and/or Bylaw Enforcement
Officer in a Compliance Notice, but not to exceed one (1) year from
submission of Cross Connection Inspection Report
(iii) Cross Connection Re-inspection Report: every five (5) years from the
date of the first report that was requested and upon change of use of the
property, change of ownership or as required by the Manager of Public
Works or Chief Building Official and/or Bylaw Enforcement Officer.
(iv)Testing of Back Flow Prevention Devices with test reports submitted to
the Town: annually or as required by the Manager of Public Works or Chief
Building Official and/or Bylaw Enforcement Officer.
(b) Residential Accounts:
(i) All new dwelling units must have a dual check valve installed, at the
property owner's cost, prior to connection to the Town of The Bancroft
Drinking Water System.
(ii) Inspection reports and scheduled testing of back flow prevention devices
shall not be required for residential units except in accordance with Part 4.2
and Part 5.4 of this By-law or when the building code requires individual or
zone protection devices to be installed.
10.
Enforcement
This By-law shall be enforced by a Building Official appointed by the Chief Building
Official or a Municipal Law Enforcement Officer employed by the Town.
11.
Penalties
11.1
Every person who contravenes any provision of this By-law, or an officer or director
of a corporation who knowingly concurs in such a contravention by the corporation,
upon conviction, is guilty of an offence and upon conviction is liable to any penalty as
provided by the Provincial Offences Act.
11.2
Where a person has been convicted of an offence, the court in which the conviction
has been entered and any court of competent jurisdiction thereafter may, in addition to
any other remedy and to any penalty imposed, make an order prohibiting the
continuation or repetition of the offence by the person convicted.
11.3
In this By-law where the Town is given the power to direct or require a person to do
a matter or thing, the Town may do the matter or thing at the person's cost if the person
defaults in doing it and the Town may recover the costs of doing the matter or thing by
action or in accordance with Section 446 of the Municipal Act.
12.
Qualified Persons
Only those persons listed in the following Authorized Functions List (Schedule A) shall
carry out the corresponding functions set out in such list.
13.
General Provisions
13.1
A building permit is required to be obtained pursuant to the Building Code Act to
install a backflow prevention device. The provisions of the Building Code Act and the
regulations pertaining to such building permit continue to apply to each installation in
addition to the provisions of this By-law.
13.2
Every owner of property upon which a backflow prevention device is installed shall
ensure that such device is in good repair at all times.
13.3
In addition to any other provision of the By-law, the Chief Building Official or
Manager of Public Works may at any time order an owner, at the owner's expense, to
8
conduct tests, provide reports and undertake any other measures required for the
prevention of backflow or cross connection.
13.4
Where a time frame is set out in this By-law for carrying out any action, the Town
may extend the time for compliance beyond the established time frame on approval by
the Manager of Public or Chief Building Official and/or By-Law Enforcement Officer.
13.5
This By-law shall come into force and take effect from the enactment thereof.
9
SCHEDULE "A" TO CROSS CONNECTION AND BACKFLOW PREVENTION POLICY
AUTHORIZED FUNCTIONS LIST
ITEM
FUNCTION
Professiona
l Engineer
(P. Eng)
with
Tester's
Certificate
* Certified
Engineerin
g
Technologi
st (C.E.T.)
with
Tester's
Certificate
Licensed
Master
Plumber
with
Contractor
and
Tester's
Certificate
**
Journeyman
Plumber with
Tester's
Certificate
***
Apprentice
Plumber with
Tester's
Certificate
Fire System
Sprinkler
Fitter with a
Tester's
Certificate
Lawn
Irrigation
System
Installer with
Tester's
Certificate
Municipal staff
within Water
and
Wastewater
Division with
Tester's
Certificate
1
Carry out Cross
Connection Survey
✓
✓
✓
✓
✓
2
Install, Relocate or
Replace Backflow
Prevention Device
✓
✓
✓
3
Repair of Backflow
Prevention Device
✓
✓
✓
✓
✓
4
Test Backflow
Prevention Device
✓
✓
✓
✓
✓
✓
✓
5
Items 1, 2, 3 & 4
above in Relation to
Fire Protection
Systems
✓
✓
✓
✓
6
Items 3 & 4 above in
Relation to Lawn
Sprinkler Systems
✓
✓
✓
✓
✓
✓
7
Items 1, 2, 3 & 4 in
relation to
municipally owned
and operated
facilities
✓
✓
✓
✓
✓
* Required to be under the direction of a Professional Engineer. ** Required to be employed by a Licensed Plumbing Contractor.
*** Required to be employed by a Licensed Plumbing Contractor and under the direct supervision of a Journeyman Plumber or Master Plumber.
10
SCHEDULE "B" TO CROSS CONNECTION AND BACKFLOW PREVENTION POLICY
Category
Required Registrations
Documentation Required
Authorized Functions
Registration #/ Fees
Plumbing
Companies
Registration
done by
Master
Plumber
Master plumber with tester's
certificate as well as all
journeyman plumbers with a
tester's certificate and all
apprentice plumbers with
tester's certificate under his/her
direction or direct supervision.
Master Plumbers License
Journeyman Plumbers: Journeyman's License
with tester's certificate issued by participating
Canadian section of the AAW.
Apprentice Plumbers: Apprenticeship contract
with Tester's certificate issued by participating
Canadian section of the AWWA.
Calibration certificate for backflow device testing
equipment.
1. Carry out cross connection surveys.
2. Install, relocate or replace backflow
preventer.
3. Test backflow preventer.
4. Repair backflow preventer.
5. Complete Items 1, 2, 3, and 4 in
relation to fire protection systems.
6. Complete Items 3 and 4 in relation to
lawn sprinkler systems.
Pay one fee for all
persons registered.
Receive one
registration number
for all persons
registered.
Fire and
Sprinkler
Companies
Master sprinkler and fire
protection installer license as
well as all journeyman sprinkler
and fire protection installers with
a tester's certificate and all
apprentice sprinkler and fire
protection installer with a tester's
certificate who are under his/her
direction or direct supervision.
Master sprinkler and fire protection installer
license.
Journeyman: Journeyman's License with
Tester's certificate issued by participating
Canadian section of the AWWA.
Apprentice: Apprenticeship contract with
Tester's certificate issued by participating
Canadian section of the AWWA.
Calibration certificate for backflow device testing
equipment.
In relation to Fire Protection Systems
Only:
1. Carry out cross connection surveys.
2. Install, relocate or replace backflow
preventer.
3. Test backflow preventer.
4. Repair backflow preventer.
Pay one fee for all
persons registered.
Receive one
registration number
for all persons
registered.
Irrigation
Contractors
Irrigation contractor as well as
all irrigation installers with a
tester's certificate under his/her
direction or direct supervision.
Lawn irrigation installer: Tester's certificate
issued by participating Canadian section of the
AWWA.
Calibration certificate for backflow device testing
equipment.
1. Repair and test backflow preventers
on irrigation systems
Pay one fee for all
persons registered.
Receive one
registration number
for all persons
registered.
Professional
Engineers/
Certified
Engineering
Technologists
Professional Engineer with
tester's certificate as well as all
Certified Engineering
Technologists with a tester's
certificate under his/her direction
or direct supervision
Professional engineer: PEO License Number.
Tester's certificate issued by participating
Canadian section of the AWWA.
C.E.T. under direct supervision of Professional
Engineer: Tester's certificate issued by
participating Canadian section of the AWWA.
Calibration certificate for backflow device testing
equipment.
1. Carry out cross connection surveys.
2. Repair and test backflow prevention
device.
Pay one fee for all
persons registered.
Receive one
registration number
for all persons
registered.
Municipal
Staff
All water and wastewater
division employees with a
tester's certificate operating
under the direction of
Professional Engineer.
Tester's certificate issued by participating
Canadian section of the AWWA.
Calibration certificate for backflow device testing
equipment.
In relation to Town facilities:
1. Carry out cross connection surveys.
2. Install, relocate or replace backflow
preventer.
3. Repair backflow preventer.
4. Test backflow preventer.
Receive one
registration number
for all persons
registered.