By-Law 09-73 1 THE CORPORATION OF THE TOWN OF GRIMSBY By-law No. 09-73 A BY-LAW TO PROTECT THE TOWN OF GRIMSBY'S DRINKING WATER DISTRIBUTION SYSTEM FROM CONTAMINATION THROUGH CROSS- CONNECTION AND BACKFLOW WHEREAS the Town of Grimsby as the Owner of the Grimsby Drinking Water Distribution System is responsible to operate, maintain and test its water distribution system in accordance with the Safe Drinking Water Act, 2002, S.O. 2002, C.32 and 0. Reg 170/03, both as amended, to ensure that all water provided by this system meets the requirements of the prescribed drinking-water quality standards; AND WHEREAS The Safe Drinking Water Act, 2002 places a Standard of Care on the Owner of the municipal drinking water distribution system; AND WHEREAS The Town of Grimsby wishes to protect its residents and other users of the Town's drinking water distribution system from deleterious and harmful contaminants that may enter the water distribution system through cross-connections and backflow. NOW THEREFORE THE COUNCIL OF THE CORPORATION OF THE TOWN OF GRIMSBY ENACTS AS FOLLOWS: 1. SHORT TITLE 1.0 This By-law may be cited as the "Backflow Prevention By-law". 2. INTERPRETATION 2.0 For the purposes of this By-law, the following terms shall have the corresponding meanings: ''Authorized Functions List" means the list of functions and the persons authorized to carry out such functions as set out in Appendix "A" of this By-law; "auxiliary water supply" means, when applied to any property or structure, any water supply on or available to the property or structure other than the Town's primary potable water supply for the property or structure; "backflow" means the flowing back of or reversal of the normal direction of flow of water; By-Law 09-73 2 "backflow device tester'' means a Person, performing or engaging to perform "Backflow Work" 'backflow prevention device" means a device that prevents backflow certified to the CSA Standard; "backflow work" includes performing building surveys to identify cross connections; selection, testing and repair of backflow prevention devices and completion of test reports and test tags for backflow prevention devices; 'building" shall have the same meaning as set out in the Ontario Building Code; "cross-connection" means any actual or potential connection between a potable water supply or system and any source of pollution or contamination and includes any by-pass, jumper connection, removable section of pipe, swivel or changeover device and any other temporary or permanent connecting arrangement through which backflow may occur; "cross-connection control survey form" means a form acceptable to the Town containing information related to the types of cross-connections, the Degree of Hazard (in accordance with Appendix "B" of this By-law) and the method of protecting those cross-connections within any building or structure. The form must also contain owner and contact information for the property; "CSA Standard" means the document entitled 864.10-071864. 10.1-07 Selection and installation of backflow preventers/Maintenance and field testing of backflow preventers published in 2007 by the Canadian Standards Association, or any successor thereof; "distribution system" means the Town of Grimsby Drinking Water Distribution System and includes appurtenances and the property service pipe as defined in the Safe Drinking Water Act, 2002, S.O. 2002, C.32 and O.Reg 170/03; "Licensed Plumber" means a Person who has been issued a Certificate of Qualification in the trade of plumber under the Trades Qualification Act and Apprenticeship Act, R.S.O. 1990, Chapter T.17, or any successor thereof; "Ontario Building Code" means Ontario Regulation 350/06 (the Ontario Building Code) or any successor thereof; By-Law 09-73 3 "owner" means any person, firm or corporation having control over property to which this By-law applies and includes the owner registered on the title of the property and any occupant of any building or structure located on such property; ''potable water" means water that is safe for human consumption; ''premise isolation" means protection provided at the entrance to a building or structure from the Town's drinking water supply; ''property" means any land within the Town of Grimsby and includes all buildings or structures; "qualified person" means a person who is accredited by a School of Accreditation as an installer and or tester of backflow prevention device; "School of Accreditation" means any school or college providing a cross- connection control course in backflow prevention device testing that has been accredited by an organization or association such as the Ontario Water Works Association or equivalent as approved by the Town; "Selection Guide" means the Backflow Prevention Device Selection Guide as set out in Appendix "B" of this By-law; "source isolation" means isolation of the water located within or having flowed through a source or potential source of contamination within a building or structure including a device, machine, water system or the like, from any potable water system; "structure" means anything constructed or built permanently or temporarily which is provided with a source of potable water; "test report" means a test report for premise isolation backflow devices acceptable to the Town containing information related to the qualified person's name, certification number, employer name. contact information, serial number of test kit and last calibration date of test kit. The test report must also contain the make, model, serial number, size, type, location, purpose, installation address and test results of the backflow prevention device. The form must also contain owner, occupant and contact information for the property; By-Law 09-73 4 "test tag" means a tag acceptable to the Town containing information related to the make, model, serial number, size, type, location, purpose, installation address and test history of the backflow prevention device; "Town" means the Corporation of the Town of Grimsby and includes its employees, servants and agents; "untreated water" means any water not subject to the requirements of the Ontario Safe Drinking Water Act 2002. S.O. 2002, C.32; "water meter" means the water meter installed within a property or structure to record the amount of water supplied to such property or structure by the; and "zone isolation" means the isolation of the water located within an area of a building or structure from any potable water system located within such building or structure. 3. APPLICATION OF BY-LAW 3.0 This By-law applies to existing industrial, commercial, institutional and multi- residential buildings and structures, except buildings or structures of residential occupancies which are of three or fewer stories in building height above ground level and having a building area - total gross floor area not exceeding 600m2 all as defined in the Ontario Building Code. 3.1 In addition to and notwithstanding section 3.0 of this By-law, this By-law applies where a condition exists in any building or structure that may be hazardous or detrimental to the potable water supply. 3.2 Where any requirements of the Ontario Building Code or any other By-law or Regulation conflict with this By-law, then the requirement which provides the highest degree of premise isolation shall apply. 4. CROSS-CONNECTION PROHIBITED 4.0 No person or owner shall connect, cause to be connected, or allow to remain connected to the Town's drinking water distribution system or any other potable water system any piping, fixture, fitting, container, appliance, vehicle, machine or the like in a manner which may under any circumstance allow untreated water, waste water or any other liquid, chemical or substance to enter such supply or system, except in compliance with the provisions of this By-law. By-Law 09-73 5 4.1 In addition to section 4.0 of this By-law and in accordance with all other provisions of this By-law, every owner of property to which this By-law applies shall ensure that a backflow prevention device is installed in respect of premise isolation, source isolation and zone isolation in every building or structure where the Town's drinking water distribution system supply or other potable water supply or connection exists. 4.2 No person or owner shall connect, cause to be connected, or allow to remain connected to the Town's drinking water distribution supply any auxiliary water supply without written approval from the Town. 4.3 No person or owner shall connect, cause to be connected or allow to remain connected either directly or indirectly to the Town's drinking water distribution system supply, any untreated water or non-potable water. 4.4 Fire protection systems connected to potable water from the water distribution system shall be protected against backflow in accordance with CSA Standard. 5. PERSONS PERMITTED TO CARRY OUT WORK 5.0 Only persons listed in the Authorized Functions List shall carry out the corresponding functions set out in such list and shall be a qualified person. 5.1 (a) every Backflow Device Tester shall have a regular place of business and shall identify to the Town the mailing address of the business property or structure; (b) every Backflow Device Tester Company shall list all employees with a current certificate from a School of Accreditation as a backflow device tester; (c) every Backflow Device Tester shall provide the following documentation at the time of the initial installation; (i) a current certificate from a School of Accreditation as a certified Backflow Prevention Device Tester for all their employees performing Backflow Work; (ii) a valid calibration certificate for testing equipment used in the testing requirements of this By-law. By-Law 09-73 6 6. APPLICATION OF CSA STANDARD 6.0 Except as otherwise set out in this By-law, the installation, maintenance and field testing of backflow prevention devices shall be in accordance with the CSA Standard. 6.1 Wherever the CSA Standard and this By-law are in conflict, the provisions which provide the highest degree of premise isolation shall apply. 7. SELECTION OF BACKFLOW PREVENTION DEVICES 7.0 Every owner of a building or structure of a type set out in Section 3 of this By-law shall, unless otherwise required by the Town, cause to be carried out a cross- connection control survey form, of each of their buildings and structures with respect to all existing cross-connections and all existing and required backflow prevention devices and: 7.0.1 shall ensure that such survey is carried out on a cross-connection control survey form by a qualified person permitted to do so pursuant to the Authorized Functions List; and, 7.0.2 shall ensure that the completed cross-connection control survey form is provided to the Town within 14 days of the survey being conducted; and, 7.0.3 shall be carried out after the passing of this By-law by the owners of all required properties and shall be submitted to the Town under section 7 .0.2, of this By-law, not later than May 1, 201 0; and, 7.0.4 shall also be carried out by the owner within 14 days of any new building, building expansion or alteration to any buildings' plumbing or operational changes that my effect the Town's drinking water distribution system. 7.1 Every owner shall ensure that every backflow prevention device required for premise isolation on their property is a testable device and is the proper device to be used pursuant to section 7 .2 of this By-law. 7.2 Backflow prevention devices for premise, source or zone isolation shall be determined: 7.2.1 using the Selection Guide; or By-Law 09-73 7 7.2.2 when the type of cross-connection is not identified in the Selection Guide, by the Town. 7.3 Despite section 7.2 of this By-law, the Town may require or permit in writing only, a particular backflow prevention device to be used in respect of any cross- connection. 7.4 Despite section 7.2 of this By-law, the Town may permit an existing backflow prevention device if previously approved but shall be approved only as long as the safety of the water supply is maintained to the satisfaction of the Town in its sole discretion. 7.5 Despite section 7.2. of this By-law, where a source isolation backflow prevention device has been installed by the manufacturer of the equipment, the cross- connection is required to be reviewed to determine if the backflow prevention device meets the requirements of the Selection Guide. These cross-connections are to be indicated on the cross-connection control survey form. 8.INSTALLATION OF BACKFLOW PREVENTION DEVICES 8.0 Every person installing a backflow prevention device shall ensure that: 8.0.1 such device is installed in accordance with manufacturers specifications and the requirements of the CSA Standard; and, 8.0.2 such device is located in such a manner so that in the event of backflow, the device prevents contamination of the Town's drinking water supply and any other potable water system; and, 8.0.3 where such device is installed in respect of premise isolation, such device is located before the first branch line leading off the water supply line and not more than 3.0 metres downstream of the water meter, except where circumstances require the device to be installed upstream of the water meter and such location is to the satisfaction of the Town; and, 8.0.4 where such device is installed in respect of premise isolation all piping between the water meter and such device is clearly labeled "no connection permitted"; and, By-Law 09-73 8 8.0.5 where such device is installed in respect of source or zone isolation, all piping between the point of contamination and the point at which the device is located, is labeled ''non-potable water". 8.1 Every owner of property upon which a backflow prevention device is installed shall ensure that such device is maintained and in proper working order at all times. 8.2 The Initial Compliance Implementation Date for the owners of all required buildings and structures existing at the date of the passing of this By-law to meet the backflow device installation requirements of this By-law shall be no later than: (i) July 1, 2010 for all properties as identified as "Severe Hazard" as defined in Appendix "B" of this By-law and identified under section 7.0 - cross- connection control survey form requirements of this By-law; and, (ii) January 1, 2011 for all properties as identified as "Moderate Hazard" as defined in Appendix "B" of this By-law and identified under Section 7.0- cross-connection control survey form requirements of this By-law. 9. TESTING OF DEVICES 9.0 Every owner who has a backflow prevention device located on his or her property shall ensure that: 9.0.1 such device is tested by a qualified person when it is first installed and shall be tested annually thereafter or at any other time when requested by the Town and also when the device is cleaned, repaired, overhauled, replaced or relocated; and, 9.0.2 a test report for a premise isolation device shall be provided to the Town within fourteen days of the test being conducted; and, 9.0.3 in the event that such device is malfunctioning or otherwise not in proper working order, the device is immediately repaired or replaced; and, 9.0.4 in the event that the water supply to the device cannot be shut down in order to facilitate annual testing, a by-pass shall be installed around the device with a suitable backflow prevention device installed in the by-pass to allow for annual testing of both devices. 9.1 Every person who tests a backflow prevention device shall carry out such testing in accordance with this By-law, the CSA Standard and all applicable legislation. By-Law 09-73 9 9.2 Every person who tests a backflow prevention device shall: 9.2.1 provide a legible test report to the owner in respect of such test; and, 9.2.2 upon completing such test, complete and affix a test tag to the device or immediately adjacent to the device on the piping connected thereto; and, 9.2.3 upon finding that such device is malfunctioning or otherwise not in proper working order, immediately notify the owner of the property of such condition in writing, and, in the case of a premise isolation device, also notify the Town immediately verbally and also immediately in writing. 10. INSPECTIONS 10.0 The Town may, at any reasonable time, enter without advance notice onto any property, building or structure to inspect for compliance with this By-law. 10.0.1 When carrying out an inspection pursuant to section 10.0 of this By-law, the Town may: (a) require the production for inspection of documents or effects relevant to the inspection. (b) inspect and remove documents or effects relevant to the inspection for the purpose of making copies or extracts. (c) require information from any person concerning a matter related to the inspection. (d) make examinations or take tests, samples or photographs necessary for the purposes of the inspection. 10.1 Where an owner does not comply with any provision of this By-law, the Town may: 10.1.1 Order the owner to comply with this By-law's requirements, and in so doing, shall provide reasonable particulars of the owner's non-compliance and prescribe the time period for compliance with such Order; 10.1.2 Shut off the water supply to the property or any portion thereof until such time as all provisions of this By-law are met. By-Law 09-73 10 11. GENERAL PROVISIONS 11.0 In addition to any other provisions of this By-law, the Town may at any time order an owner to conduct tests, provide reports and undertake any other measures required for the prevention of backflow or protection of a cross-connection. 11.1 Appendices "A" (Authorized Function List) & "B" (Backflow Prevention Device Selection Guide) shall form part of this By-law. READ A FIRST TIME THIS 21st day of September 2009. READ A SECOND AND THIRD TIME AND FINALLY PASSED THIS day of , 2009 By-Law 09-73 11 Appendix "A" To By-Law Number 09-73 of The Corporation of the Town of Grimsby Authorized Function List Item FUNCTION LICENCED PLUMBER WITH TESTER'S QUALIFICATIONS * JOURNEYMAN PLUMBER WITH TESTER'S QUALIFICATIONS ** APPRENTICE PLUMBER WITH TESTER'S QUALIFICATIONS FIRE SYSTEM SPRINKLER FITTER WITH A TESTER'S QUALIFICATIONS LAWN IRRIGATION SYSTEM INSTALLER WITH TESTER'S QUALIFICATIONS 1 Carry Out Cross- connection Control Survey ✓ ✓ 2 Install, Relocate or Replace I Backflow Prevention Device ✓ ✓ ✓ 3 Repair of Backflow Prevention Device ✓ ✓ ✓ ✓ 4 Test Backf/ow Prevention Device ✓ ✓ ✓ ✓ 5 Items 1,2, 3 & 4 above in Respect of Fire Protection Systems ✓ ✓ ✓ ✓ 6 Items 2 (up to 1"), 3 & 4 above in Respect of Lawn Sprinkler System ✓ ✓ ✓ ✓ * Required to be employed by a Licenced Plumbing Contractor ** Required to be employed by a Licenced Plumbing Contractor By-Law 09-73 12 APPENDIX "B" to By-Law No. 09-73 of the Corporation of the Town of Grimsby BACKFLOW PREVENTION DEVICE SELECTION GUIDE INTERPRETATION In addition to those terms defined in section 2.0 of By-law No. 09-73, the following terms shall have the corresponding meanings for the purposes of this Appendix: "air gap (AG)" means the unobstructed vertical distance through air between the lowest point of the water supply outlet and the flood level rim of the fixture or device into which the outlet discharges; "back siphonage" means backflow caused by pressure below atmospheric in the supply system; "double check valve assembly (DCVA)" means a backflow prevention device consisting of two force-loaded, independently acting check valves, including tightly closing resilient-seated shutoff valves located at each end of the assembly and fitted with properly located resilient-seated test cocks. This device is designed for use under continuous pressure; "dual check valve {DuC) " means a backflow prevention device consisting of two independently acting, force-loaded, soft-seated check valves in series. This device does not have a relief port or test cocks. This device is designed for use under continuous pressure; "dual check valve with atmospheric port (DCAP), (DCAPC)" means a backflow prevention device that consists of two independently acting check valves separated by an intermediate chamber with an atmospheric port. A chamber pressure higher than the supply pressure is required to open the port when there is a positive pressure on the supply side. This device is designed for use under continuous pressure; (DCAPC) is specifically designed for use in carbonated beverage dispensing machines; "dual check valve with intermediate vent {DuCV)" means a backf/ow prevention device that consists of two independently acting check valves biased to a normally closed position. Between the check valves there is a relief port that is biased to a normally open position. This device is designed for use under continuous pressure; By-Law 09-73 13 "reduced pressure principle assembly (RP)" means a backflow prevention device that consists of a mechanically independently acting, hydraulically dependent relief valve located in a chamber between two independently operating, force-loaded check valves, the intermediate chamber pressure always being lower than the supply pressure when there is a positive pressure on the supply side. The unit includes properly located resilient-seated test cocks and tightly closing resilient-seated shutoff valves at each end of the assembly. This device is designed for use under continuous pressure; "minor hazard" means any cross-connection or potential cross-connection that constitutes only a nuisance, with no possibility of any health hazard; "moderate hazard" means any minor hazard that has a low probability of becoming a severe hazard; "severe hazard" means any cross-connection or potential cross-connection involving any substance that could be a danger to health; "single check valve" (SCVAF) means a backflow preventer that consists of one force- loaded, independently acting check valve, including resilient-seated shut-off valves located at each end of the SCVAF backflow preventer and fitted with resilient􀃘seated test cocks. SCVAF backflow preventers are designed for use under continuous pressure on fire sprinkler and standpipe systems; "vacuum breaker'' means a device that will prevent backflow when pressure in the system upstream of the device falls below atmospheric pressure. Air is only admitted downstream of the device; "vacuum breaker, atmospheric type (AVB)" means a vacuum breaker designed to be under pressure only when water is being drawn from the system and for short, intermittent periods of time; "vacuum breaker, laboratory faucet type (LFVB)" means a vacuum breaker consisting of two independently acting check valves force-loaded or biased to a normally closed position. Between the check valves there is a relief port that is force-loaded or biased to a normally open position. When the laboratory faucet is off, the check valves are closed and the port is open; when the faucet is on, the check valves are open and the port is closed; and "vacuum breaker, pressure type (PVB)" or "spill resistant pressure type (SRPVB)" means an assembly containing an independently acting check valve force-loaded or By-Law 09-73 14 biased, to a normally closed position, and an independently operating air inlet valve force-loaded or biased to a normally open position and located on the discharge side of the check valve. The assembly is equipped with properly located resilient-seated test cocks and tightly closing resilient-seated shutoff valves located at each end of the assembly. The device is designed for use under continuous pressure. APPENDIX "B" to By-Law No. 09- 73 of the Corporation of the Town of Grimsby Selection Guide for Backflow Preventers Degree of Hazard Type of Device CSA Standard Designation Minor Moderate Severe Device Under Continuous Pressure Air gap ✓ ✓ ✓ No AVB B64.1.1 ✓ ✓ ✓* No DCAP B64.3 ✓ ✓† -- Yes DCAPC B64.3.1 ✓ ✓ -- Yes DCVA B64.5 ✓ ✓ -- Yes DuC B64.6 ✓ -- -- Yes DuCV B64.8 ✓ ✓† -- Yes HCDVB B64.2.11.1 ✓ ✓† ✓* No HCVB B64.2 ✓ ✓† ✓* No LFV8 B64.7 ✓ ✓† ✓* No PVB B64.1.2 ✓ ✓ ✓ Yes RP B64.4 ✓ ✓ ✓ Yes SRPVB B64.1.3 ✓ ✓ ✓ Yes *When the recommended backflow preventer is used for this degree of hazard. Zone protection with an RP backflow preventer or an air gap shall also be required. † When the recommended. device is used for this degree of hazard, zone or area protection with a DCVA backflow preventer, RP backflow preventer, or an air gap shall also be required. By-Law 09-73 15 APPENDIX "B" to By-Law No. 09-73 of the Corporation of the Town of Grimsby BACKFLOW PREVENTION GUIDE TO DEGREE OF HAZARD Type of Cross Connection Degree of Hazard Type of Cross Connection Degree of Hazard Agricultural chemicals (sprayers) Severe Garbage disposal unit Severe Air compressor oil cooler Moderate Garbage can washer Severe Animal watering Moderate Heat Exchanger Moderate to Severe Aspirator (toxic) Severe Heating System (copper/plastic: no chemicals) Minor Aspirator (non- toxic) Moderate Heating System (no chemicals added} Moderate Autoclave Severe Heating System (chemicals added) Severe Autopsy and mortuary equipment Severe Heating System (single family dwelling) Moderate Auxiliary water supply Severe Hose bib sediment faucet Minor to Severe Baptistery Moderate Hose bib, sediment faucet, connected to high hazard Severe Basin Moderate Hose bib, sediment faucet (residential) Minor to Moderate Bathtub (all) Moderate Humidifier Moderate Bedpan washer Moderate Humidifier with sump Severe Beverage dispensing equipment (no carbonator) Minor Hydrotherapy bath Severe Beverage dispensing equipment (with carbonator) Minor Ice Machine for commercial restaurant Moderate to Severe By-Law 09-73 16 Type of Cross Connection Degree of Hazard Type of Cross Connection Degree of Hazard Bidet Moderate to Severe Ice making equipment for sports arena Severe Bottle Washer Moderate to Severe industrial fluid system Severe Bread Making equipment Minor to Moderate irrigation system (chemical injected) Severe Canopy washer Severe Irrigation system (no chemical added) Moderate Chemical Feed Tank Severe Lab bench equipment (toxic) Severe Chiller tank (no chemical) Moderate to Severe Lab bench equipment (non toxic) Minor Chiller tank (with chemical) Severe Laboratory Severe Chlorinator Severe Laboratory Faucet Moderate to Severe Clothes washer (residential) Moderate laundry, commercial coin-operated Moderate Coffee machine Minor Laundry machine commercial Moderate Condensate tank (top feed) Moderate Laundry machine residential Minor Condensate tank Severe Laundry tub faucet with hose bib connection Moderate Cooking Kettle Minor Lavatory Moderate Cooling Condenser (solenoid upstream) Minor Lethal substance Severe Cooling Condenser (solenoid downstream) Severe Livestock equipment Severe Cooling Tower Severe Mixing tee with steam and water Moderate Deaerator (Top Feed) Moderate Mop sink faucet with hose bib connection Moderate Deaerator (Bottom Feed) Severe Mortuary or Morgue Severe By-Law 09-73 17 Type of Cross Connection Degree of Hazard Type of Cross Connection Degree of Hazard Degreasing equipment system Severe Non-portable water Severe Deionized water Severe Optician or Ophthalmology equipment Minor to Moderate Dental Vacuum pump Severe Photo lab sink Severe Dental Cuspidor (with internal air gap) Minor Pipette washer Severe Dental Cuspidor (no air gap) Severe Piping to chemical dispensers Minor to Severe Dental Delivery System Minor Plating tank Severe Detergent dispenser Severe Potato peeler Moderate Dipper well in ice- cream parlour or restaurant Moderate Poultry barn Severe Dish rinse unit with flex hose Moderate Pressure washer (no aspirator) Minor Dishwasher (commercial) Moderate Pressure washer (with aspirator) Severe Dishwasher (residential) Minor to Moderate Private fire hydrant Moderate Distiller Minor Private water source Severe Dockside Marine Facility Severe Pump pr1mer line (toxic) Severe Dry sprinkler or standpipe system Moderate Pump primer line (non-toxic) Moderate Fire Hydrant Moderate Radiator flushing equipment Severe Flexible shower head with hose Minor to Severe Restricted area Severe By-Law 09-73 18 Type of Cross Connection Degree of Hazard Type of Cross Connection Degree of Hazard Floor drain with flushing rim Severe Reverse osmosis Minor Flush Tank Moderate Reverse osmosis with backwashing Moderate Flushing equipment device Severe Reverse osmosis with chemical cleaning Severe Flushometer Severe Serrated faucet Severe Fountain, ornamental Moderate to Severe Sewage ejector Severe Fountain, ornamental (chemical added Severe Sewage pump Severe Fume hood Severe Shampoo sink Moderate Sizing vat Severe Wash rack Severe Solar energy unit Severe Wash tank Moderate Solution tank Severe Wash tank (toxic) Severe Spa or Hot Tub Moderate Water Closet (tank/type)(N/A if constructed after 1995) Moderate Specimen Tank Severe Water closet (flushometer type) Moderate Steam table Minor to Moderate Water hauling equipment (non- toxic) Moderate Steam generator Moderate Water hauling equipment (toxic) Severe Steam cleaner Moderate Water softener (commercial) Minor Sterilizer (condensate cooling only) Moderate Water softener drain Severe Still Minor Wok table (for oriental cooking with submerged inlet) Moderate By-Law 09-73 19 Type of Cross Connection Degree of Hazard Type of Cross Connection Degree of Hazard Swimming Pool (residential) Minor Swimming pool (other than residential) Moderate Swimming Pool (direct connect) Moderate Swimming pool makeup tank Moderate Teeth cleaning equipment (veterinary type) Moderate Trap primer Sever Vending machine with no carbonators Minor Emergency eyewash/Shower - this equipment must be installed upstream of all zone and source isolation Fire Protection Systems.: General Conditions Antifreeze solutions must be water solutions of pure glycerin (C.P. or U.S.P., 96.5% grade) OR propylene glycol conforming to action 3-5.2.1 of NFPA-13, 1994 Edition. These are best described as food-grade chemicals. Antifreeze solutions must be tested to verify compliance with above conditions. Any other antifreeze solution is NOT permitted and must be replaced Expansion chambers shall be of an appropriate size to compensate for thermal expansion of antifreeze solution. An adequate amount of piping before or after the location of any backflow prevention device shall be Increased In size to compensate for the pressure loss created by the device being installed. The flows are to be in accordance with NFPA-13 for the appropriate hazard classification In the area downstream of the backflow prevention device. By-Law 09-73 20 Table 7.6.2.4 Backflow Prevention Devices on fire Sprinkler and Standpipe Systems Form Part of Sentences 7.6.2.4.(2) Column 1 Column 2 Column 3 Column 4 Column 5 Column 6 CSA Standard Number Type of Device System made with Portable Water System Materials System Not made with Portable Water System Materials Minor Hazard (2) Residential Partial Flow- Through System Minor Hazard (2) Class 1 System Moderate Hazard (2) Class 1,2,3 and 6 Severe Hazard (2) Any Class of System in which Antifreeze or Other Additives are used B64.6.1 DuC P NP NP NP B64.9 SCVA P P NP NP B 64.5.1 DCVA P P P NP B64.4.1 RP P P P P Notes to Table 7.6.2.4.: P -Permitted NP -Not Permitted (1)-The product la only permitted for use on fire sprinkler and standpipe systems. (2)-Minor Hazard, Moderate Hazard and Severe Hazard have the same meaning as Indicated in Can/CSA-S64.10 -Manual for the Selection and installation of Backflow Prevention Devices"". APPENDIX 11 811 to By-Law No. 09- 73 of the Corporation of the Town of Grimsby BACKFLOW PREVENTION GUIDE TO DEGREE OF HAZARD -PREMISE ISOLATION Type of Building Degree of Hazard Type of Building Degree of Hazard Abattoir (slaughter house) Severe Paint manufacturing plant Severe Airport Moderate Penitentiary Moderate Animal feed lot Moderate to Severe Petroleum processing or storage facility Severe By-Law 09-73 21 Animal stock yard Moderate to Severe Pharmaceutical manufacturing facility Severe Apartment building (within- the scope of Part 3 of the Ontario Building Code·) Moderate to Severe Photo processing facility Severe Aquaculture farm Severe Plant using radioactive material Severe Aquarium public} Severe Plastic manufacturing plant Severe Arena Moderate Platina shop Severe Asphalt plant Severe Poultry Shop Severe Auto body shop Severe Power generating facility Severe Auto dealership Moderate Premise where access prohibited Severe Automotive Plant Severe Printing plant Severe Automotive repair shoo Severe Pulp and/or paper plant Severe Beverage processing plant Severe Radiator shop Severe Blood clinic Severe Recycling facility Severe Camp site Moderate Refinery, petroleum Processing Severe Camp site with RV hookups or dump station Severe Rendering facility Severe Carwash Severe Research building Severe Church Moderate Residential premises-multi- tenant Moderate College Moderate Restaurant Moderate Commercial premises Moderate to Severe School Moderate Concrete plant Severe Sewage dump station Severe Dental office Moderate Sewage treatment plant Severe Dental surgery facility Severe Steam boiler plant Severe Dockside marine facility Severe Steel manufacturing plant Severe Dry cleaning plant Severe Storage Warehouse Moderate By-Law 09-73 22 Dry cleaning facility (no dry- cleaning process on premise) Moderate Swimming pool facility Moderate Duplex housing with shared service Minor Technical institute Moderate Dye plant Severe Townhouse (shared service) Minor Exhibition ground Severe Track-side facilities for trains Severe Farm Moderate to Severe University Moderate to Severe Film processing faculty Severe Veterinary clinic Moderate to Severe Fire Service main connected to more than one of the following different sources of supply: (I) City water supply system (II) a private water supply system or (III) a source of non- portable water Moderate to Severe Veterinary clinic (special equipment) Severe Fire station Moderate to Severe Waste disposal Severe Fish farm or Hatchery Severe Waste water facility Severe Food processing plant Severe Waste water pump station Severe Fuel dispensing facility Moderate Waste Water Treatment Plant Severe Funeral Home Moderate to Severe Water filling station Severe Garbage transfer facility Severe Water park Moderate Golf course Moderate to Severe Water treatment plant Severe Grocer Moderate Water treatment pump station Severe Hair salon Moderate Zoo Severe Hospital Severe Hotel Moderate Industrial and Institutional Moderate to Severe Kennel Moderate Laboratory Severe Laundry (commercial) Severe By-Law 09-73 23 Laundry) commercial coln- operated) Moderate Mall - multi-tenant Moderate Manufacturing Plant (not specified) Moderate Marina (pleasure boat) Moderate to Severe Meat Packing plant Severe Medical clinic (non surgical) Moderate Medical clinic (surgical) Severe Milk processing plant Severe Mining facility Severe Mobile home park Moderate Mortuary or morgue Severe Motel Moderate Motor cycle repair facility Severe Nursing Home Moderate Office Building Moderate Oil Refinerv Severe