MUNICIPALITY OF LEAMINGTON
BY-LAW 281-01
Being a by-law to provide for backflow
prevention and to regulate the connection of
water services to the municipal water
system.
WHEREAS Section 7 of the Building Code Act, S.O. 1992 c. 23, as amended,
authorizes the Council of a Municipality to enact by-laws to provide for classes of
permits including permits in respect of any stage of construction.
AND WHEREAS Part 1 of the Public Utilities Act R.S.O. c.P 52., as amended,
authorizes the Council of a Municipality to enact by-laws to regulate supply and to
prohibit wrongful use of water in order to ensure the security of the municipal water
system.
AND WHEREAS the Council for the Municipality of Leamington deems it
necessary to provide for backflow prevention to protect the safety of the municipal water
supply.
NOW THEREFORE THE CORPORATION OF THE MUNICIPALITY OF
LEAMINGTON BY ITS COUNCIL ENACTS AS FOLLOWS:
INTERPRETATION
1 In this by-law:
1) "Authorized Functions List" means the list of functions and the persons
authorized to carry out such functions as set out as Schedule A of this By-law;
2) "Auxiliary Water Supply" means any water source or system, other than the
Municipal water supply, that may be available in a building or on any property;
3) "Backflow" means the reversal of the normal direction of flow of water;
4) "Backflow Prevention Device" means a device that prevents backflow;
5) "Building" shall have the same meaning as set out in the Building Code Act, S.O.
1992, chap. 23, as amended, or any successor thereof;
6) "Building Code" shall have the same meaning as set out in the Building Code
Act, S.O. 1992, chap. 23, as amended, or any successor thereof;
7) "Chief Building Official" shall mean the Chief Building Official appointed by the
Council for The Corporation of the Municipality of Leamington;
8) "Cross-Connection" means any actual or potential connection between a potable
water supply or system and any source of pollution or contamination and
includes any by-pass, jumper connection, removable section of pipe, swivel or
changeover device and any other temporary or permanent connecting
arrangement through which backflow may occur;
9) "Cross-Connection Survey Form" means the form set out as Schedule B of this
By-law;
10) "CSA Standard" means the standards established for backflow prevention in
Article 7.2.10.10 of the Building Code;
11) "Installation Guide" means the installation drawings governing the installation of
backflow prevention devices as set out in the CSA Standard, as amended from
time to time;
Page 2
Backflow Prevention By-law 281-01
12) "Municipality" means The Corporation of the Municipality of Leamington;
13) "Municipal Water Supply" means the municipally owned and maintained potable
water distribution system;
14) "Owner" means any person, firm or corporation having control over property to
which the By-law applies and includes the owner registered on the title of the
property and any occupant of any building or structure located on such property;
15) "Potable Water" means water that is safe for human consumption;
16) "Premises Isolation" means isolation of the water located within a building or
structure from the Municipality's water supply;
17) "Selection Guide" means the Backflow Prevention Device Selection Guide set
out in the CSA Standard, as amended from time to time;
18) "Source Isolation" means isolation of the water located within or having flowed
through a source or potential source of contamination within a building or
structure including a device, machine, water system or the like, from any potable
water system;
19) "Structure" means anything constructed or built permanently or temporarily
which is provided with a source of potable water;
20) "Tester" means a person who is licensed as tester of backflow prevention
devices;
21) "Test Report" means a report in the form set out in the CSA Standard, as
amended from time to time;
22) "Test Tag" means a tag in the form set out as Schedule C of this By-law;
23) "Water Meter" means the water meter installed within the premises to record the
amount of water supplied to such premises by the Municipality; and
24) "Zone Isolation" means the isolation of the water located within an area of a
building or structure from any potable water system located within such building
or structure.
APPLICATION OF BY-LAW
2(1) This By-law applies to existing agricultural, industrial, commercial, institutional and
residential buildings and structures,
(2) In addition to and notwithstanding section 2(1) of this By-law, this By-law applies
where a condition exists that may be hazardous or detrimental to the municipal
water supply.
CROSS-CONNECTION PROHIBITED
3(1) No person or owner shall connect, cause to be connected, or allow to remain
connected to the Municipality's water supply any piping, fixture, fitting, container,
appliance, vehicle, machine or the like in a manner which may under any
circumstance allow water, waste or any other liquid, chemical or substance to enter
such supply or system, except in compliance with the provisions of this By-law.
(2) Every owner of property to which this By-law applies shall ensure that a backflow
prevention device is installed in respect of premises isolation, source isolation and
zone isolation in every building or structure where a Municipality's water supply
exists.
(3) No person or owner shall connect, cause to be connected, or allow to remain
connected to the Municipality's water supply any auxiliary water supply.
Page 3
Backflow Prevention By-law 281-01
PERSONS PERMITTED TO CARRY OUT WORK
4 Only the persons listed in the Authorized Functions List shall carry out the
corresponding functions set out in such List.
APPLICATION OF CSA STANDARD
5(1) Except as otherwise set out in this By-law, the installation, maintenance and field
testing of backflow prevention devices shall be in accordance with the CSA
Standard.
(2) Wherever the CSA Standard and this By-law are inconsistent, the provisions of this
By-law shall prevail.
SELECTION OF BACKFLOW PREVENTION DEVICES
6(1) Every owner of a building or structure of a type set out in section 2 of this By-law
shall, every five years or as otherwise required by the Municipality, cause to be
carried out a survey of each of the owners buildings and structures with respect to all
existing cross-connections and all existing and required backflow prevention devices
according to CSA Standard:
(2) Every owner shall ensure that every backflow prevention device required on the
owners property is a testable device and is the proper device to be used pursuant to
CSA Standard.
(3) Notwithstanding section 6(2) where a source backflow prevention device has been
installed by the manufacturer of equipment using potable water for an operating
process of said equipment, the cross-connection is required to be reviewed by the
surveyor to determine if the backflow prevention device has not been compromised in
any way by the installation of equipment, piping, relocation or removal of backflow
prevention device and/or repair and maintenance of said device or equipment.
Testable backflow prevention devices are subject to Section 9 of this By-law. Cross
Connections of this type are required to be included on the Cross Connection Survey
form.
INSTALLATION OF BACKFLOW PREVENTION DEVICES
7 No person shall install a backflow prevention device unless a permit has been issued
therefore by the Chief Building Official:
OWNERS OBLIGATIONS
8(1) Every owner of property on which a backflow prevention device is installed shall
ensure that such device is in proper working order at all times.
8(2) Every owner who has a backflow prevention device located on the owner's property
shall ensure that:
a) such device is tested by a tester when it is first installed and annually
thereafter or when requested by the Municipality and also when it is cleaned,
repaired, overhauled or relocated;
b) in the event that such device is malfunctioning or otherwise not in proper
working order, the device is immediately repaired or replaced.
TESTING OF DEVICES
9(1) Every person who tests a backflow prevention device shall carry out such testing in
accordance with this By-law and the CSA Standard.
Page 4
Backflow Prevention By-law 281-01
(2) Every person who tests a backflow prevention device shall:
a) within 14 days of carrying out such test, provide a legible Test Report to the
Municipality in respect of such test;
b) upon finding that such device is malfunctioning or otherwise not in proper
working order, immediately notify the owner of the premises and the
Municipality of such condition.
INSPECTIONS
10(1) The Municipality may at any reasonable time enter onto the property of any owner
to inspect for compliance with the By-law.
(2) Where the Municipality finds that a cross connection exists on any property that
may allow contamination of the municipal water supply then the Chief Building
Official may take either or both of the following actions:
a) order the owner to eliminate the condition and in doing so may prescribe the
time period for compliance with such Order; or
b) shut off the Municipal water supply to the property or any portion thereof until
the condition is eliminated.
GENERAL PROVISIONS
11(1) In addition to any other provision of this By-law, the Municipality may at any time
order an owner to conduct tests, provide reports and undertake any other measures
required for the prevention of backflow of water into the municipal water supply.
(2) Schedule A through C inclusive shall form part of this By-law.
PENALTY
12(1)Every person who contravenes any provision of this By-law or fails to comply with
an Order issued by the Chief Building Official pursuant to this by-law is guilty of
an offence, and upon conviction is liable for a fine pursuant to the provision of the
Provincial Offences Act, R.S.O., 1990, c.P. 33, as amended.
(2)Any contravention of this By-law shall constitute a separate offence for each day
that contravention continues.
READ A FIRST, SECOND AND THIRD TIME AND FINALLY ENACTED THIS
10th DAY OF September , 2001.
Signature on file
DAVE WILKINSON
Mayor
Signature on file
BRIAN R. SWEET
Municipal Clerk
SCHEDULE "A"
of By-law 281-01
AUTHORIZED FUNCTIONS LIST
ITEM
FUNCTION
Professional
Engineer with
Tester's Licence
* Certified
Engineering
Technologist with
Tester's Licence
Licensed Master
Plumber with
Contractor and
Tester's Licence
** Journeyman
Plumber with
Tester's Licence
*** Apprentice
Plumber with
Tester's Licence
Fire System
Sprinkler Fitter
with a Tester's
Licence
Lawn Irrigation
System Installer
with Tester's
Licence
1
Carry out Cross Connection
Survey
2
Install, Relocate or Replace
Backflow Prevention Device
3
Repair of Backflow
Prevention Device
4
Test Backflow Prevention
Device
5
Items 1, 2, 3 & 4 above in
Respect of Fire Protection
Systems
6
Items 3 & 4 above in Respect
of Lawn Sprinkler Systems
*
Required to be under the direction of a Professional Engineer.
**
Required to be employed by a Licensed Pluming Contractor.
***
Required to be employed by a Licensed Plumbing Contractor and under the direct supervision of a Journeyman Plumber or Master Plumber.
NOTE: A building permit is required pursuant to the Building Code Act to install
a backflow prevention device. The provisions or the Act pertaining to such
building permit continue to apply to each installation in addition to the provisions
of this by-law. Permits are required for devices as noted in the Cross-Connection Survey Form.
SCHEDULE "B"
Of
By-law 281-01
CROSS-CONNECTION SURVEY FORM
Plumbing System π Fire Protection System π
Date (Y/M/D)
Page #
Facility:
Address:
Owner:
Report Given to:
Surveyor:
Licence #:
Phone #:
Location of Cross Connection
Existing
Protection
Type
Serial #
(If
Applicable)
Date of Last
Test (If
Applicable)
Acceptable
Protection
Yes/No
Required
Upgrade
Selection
From
REMARKS
PREMISE
PREMISE
1
2
3
4
5
6
7
8
9
10
AG - Air Gap
*AVB - Atmospheric type Vacuum Breaker
*DCAP - Dual Check Valve Type with Atmospheric Port
*DCVA - Double Check Valve Assembly Type
*DUC - Double Check Valve Type
*DUCV - Dual Check Valve Type with Intermediate Vent
HCVB - Hose Connection Type Vacuum Breaker
*LACV - Listed Alarm Check Valve
LFVB - Laboratory Faucet Type Vacuum Breaker
N - None
*PVB - Pressure Type Vacuum Breaker
*RSCV - Resilient Seated Check Valve
*RP - Reduced Pressure Principle Type
* - Building Permits required for the installation of these devices
NOTE: Surveyor required to submit copies of this report to Municipality of Leamington and owner of property.
SCHEDULE "C"
Of
By-law 281-01
TEST TAG
Front of Tag
Municipality of Leamington
38 Erie Street South
Leamington, Ontario, N8H 2Z3
(519) 326-5761
DATE INSTALLED
BACKFLOW PREVENTION ASSEMBLY TAG
YY
MM
DD
ADDRESS
TYPE OF ASSEMBLY
Π RP πDCVA πPVB
MANUFACTURER
SIZE
MODEL NUMBER:
SERIAL NUMBER"
LOCATION:
DO NOT REMOVE
Reverse side of tag
TEST DATE
YY MM DD
TESTER'S COMPANY
TESTER'S
NO.
TESTER'S
INITIALS
DO NOT REMOVE
BACKFLOW PREVENTION DEVICE SELECTION GUIDE
APPENDIX "D"
By-law 281-01
INTERPRETATION
In addition to those terms defined in section 2.0 of By-law #281-01, the following terms
shall have the corresponding meanings for the purposes of this Appendix:
"air gap (AG)" means the unobstructed vertical distance through air between the lowest
point of the water supply outlet and the flood level rim of the fixture or device into which
the outlet discharges;
"back siphonage" means backflow caused by pressure below atmospheric in the supply
system;
"double check valve assembly (DCVA)" means a backflow prevention device consisting
of two force-loaded, independently acting check valves, including tightly closing
resilient-seated shutoff valves located at each end of the assembly and fitted with
properly located resilient-seated test cocks.
"dual check valve (DuC)" means a backflow prevention device consisting of two
independently acting, force-loaded, soft-seated check valves in series. This device does
not have a relief port or test cocks. This device is designed for use under continuous
pressure;
"dual check valve with atmospheric port (DCAP)" means prevention device that consists
of two independently acting check valves separated by an intermediate chamber with an
atmospheric port. A chamber pressure higher than the supply pressure is required to open
the port when there is a positive pressure on the supply side. This device is designed for
use under continuous pressure;
"dual check valve with intermediate vent (DuCV)" means a backflow prevention device
that consists of two independently acting check valves biased to a normally closed
position. Between the check valves there is a relief port that is biased to a normally open
position. This device is designed for use under continuous pressure;
"reduced pressure principle assembly (RP)" means a backflow prevention device that
consists of a mechanically independently acting, hydraulically dependent relief valve
located in a chamber between two independently operating, force-loaded check valves,
the intermediate chamber pressure always being lower than the supply pressure when
there is a positive pressure on the supply side. The unit includes properly located
resilient-seated test cocks and tightly closing resilient-seated shutoff valves at each end of
the assembly. This device is designed for use under continuous pressure;
"minor hazard" means any cross-connection or potential cross-connection that constitutes
only a nuisance, with no possibility of any health hazard;
"moderate hazard" means any minor hazard that has a low probability of becoming a
severe hazard;
"severe hazard" means any cross-connection or potential cross-connection involving any
substance that could be a danger to health;
"vacuum breaker" means a device that will prevent backflow when pressure in the system
upstream of the device falls below atmospheric pressure. Air is only admitted
downstream of the device;
Page 2
Appendix "D" - Backflow Prevention Device Selection Guide - By-law 281-01
"vacuum breaker, atmospheric type (AVB)" means a vacuum breaker designed to be
under pressure only when water is being drawn from the system and for short,
intermittent periods of time;
"vacuum breaker, hose connection type (HCVB)" means a vacuum breaker consisting of
a single force-loaded check valve biased to a normally closed position. Downstream of
the check valve is a means of automatically venting to atmosphere that is force-loaded or
biased to a normally open position. If there is no flow through the device, the check
valve is closed and the vent is open. The device is designed to be under pressure only
when water is being drawn form the system and for short, intermittent periods of time;
"vacuum breaker, laboratory faucet type (LFVB)" means a vacuum breaker consisting of
two independently acting check valves force-loaded or biased to a normally closed
position. Between the check valves there is a relief port that is force-loaded or biased to a
normally open position. When the laboratory faucet is off, the check valves are closed
and the port is open; when the faucet is on, the check valves are open and the port is
closed; and
"vacuum breaker, pressure type (PVB)" means an assembly containing an independently
acting check valve force-loaded or biased, to a normally closed position, and an
independently operating air inlet valve force-loaded or biased to a normally open position
and located on the discharge side of the check valve. The assembly is equipped with
properly located resilient-seated test cocks and tightly closing resilient-seated shutoff
valves located at each end of the assembly. The device is designed for use under
continuous pressure;
ONTARIO COURT OF JUSTICE
PROVINCIAL OFFENCES ACT
PART I
IT IS ORDERED pursuant to the provisions of the Provincial Offences Act and the
rules for the Ontario Court of Justice that the amour;tt set opposite each of the
offences in the schedule of offences under the Provincial Statutes and Regulations
thereunder and Municipal By-law No. 281-01 of the Municipality of Leamington,
attached hereto is the set fine, for those offences. This Order is to take effect
October 12, 2005.
Dated at London this 12th day of October, 2005.
Alexander M. Graham
Regional Senior Justice
West Region
Schedule "B" to Report CL/31/05
Set Fine Schedule
THE CORPORATION OF THE MUNICIPALITY OF LEAMINGTON
Part 1 Provincial Offences Act
By-law 281-01: Being a by-law to provide for backflow prevention and to regulate the connection of water
services to the municipal water system.
ITEM
SHORT FORM WORDING
OFFENCE CREATING
PROVISION
SET FINE
1
Permit improper connection to water supply.
3(1)
$100.00
2
Fail to install backflow prevention device.
3(2)
$100.00
3
Permit connection of auxiliary water supply.
3(3)
$100.00
4
Function completed by unauthorized person.
4
$100.00
5
Permit improper backflow prevention device.
6(2)
$100.00
6
Fail to have required survey completed.
6(1)
$100.00
7
Install backflow prevention device without permit.
7
$100.00
8
Fail to maintain backflow prevention device.
8(1)
$100.00
9
Fail to have backflow prevention device tested.
8(2)a
$100.00
10
Fail to have malfunctioning backflow prevention device replaced.
8(2)b
$100.00
11
Fail to provide test report.
9(2)a
$100.00
12
Fail to provide notification of malfunctioning device.
9(2)b
$100.00
Penalty Provision for the offences indicated above is Section 12(1) of By-law No. 281-01 a certified copy of which has been filed.
File S:\Corporate\C00-Council&By-laws\C01-By-laws\2001 Bylaws\281-01-Set Fine Schedule for Prov-Backflow.doc